Written by: A.C. Amended by GG
Checked by: JBJ
Document Number: USDISC Rev.: 3
Page 39 of 47
19/07/2004
5. Enter the loop number and press enter. Enter the point address number and
press enter. The following screen will be displayed:
ADR VAL TYPE STS CMD
001 025 HEAT 000 000
ZONE001 CMD BITS=321
4=PREV,5=NEXT,<=EXIT
6. To display other points press 4 or 5 to change the device number. To view
devices on another loop press escape to return to the previous menu screen.
Upon exiting the status mode the command bits are returned to panel control. If a
device has undergone a self test in the disabled status mode the panel may detect a
fire condition before the analogue value returns to normal.
How To Test Devices Using One Person Test Mode
In this test any fire event within any of the selected zones will not be reported on the
panel display, but is printed and recorded in the event log with the description "TEST”
instead of “FIRE”. No relays or cause/effect will be operated, but the sounders may
operate for ten seconds if the appropriate mode is selected. The LED on the point in
fire will illuminate for ten seconds. Any fire events from other zones will clear the
menu page from the screen in order to report the genuine fire. If this occurs it will be
necessary to re-enter the menu system. As soon as point walk test is selected the
currently selected test zones will be identified.
1. Enter the user menu as described in section 6.
2. Press 5 to select option 5 - Test. The following screen will be displayed:
TEST MODE
1=VIEW POINT STATUS
2=ONE PERSON TESTS
SELECT 1..2, <=EXIT
3. Press 2 to enter the one person test mode. The following screen will be
displayed:
ONE PERSON TEST
1=POINT WALK TEST
2=ALARM WALK TEST
SELECT 1..2, <=EXIT
Device address
Analogue value
Device type
Status bits returned by
device. Bit 2 is displayed on
the left, bit 0 on the right.
Command bits transmitted
to device. These are
displayed in the order bit 2
on the left, bit 0 on the right.
Zone number
Keys to toggle the command bits:
Bit 2 is toggled by key 3;
bit 1 is toggled by key 2;
bit 0 is toggled by key 1.