4. Enter panel number.
CONTROL FROM PAN.001
1=SILAL–1, 2=RESET-1
3=TSTAL-1, 4=EVAC -1
5=CLR.-1,>=NXT,<=END
5. Pressing 1, 2, 3, 4 or 5 will toggle the value opposite the corresponding user control
type between values 0, 1. (1 = silence alarms, 2 = reset system, 3 = test alarms, 4 =
evacuate, 5 = reset faults) These values have the following meaning:-
0 = ignore controls in this category.
1= react normally to controls in this category.
6. Pressing > will display the values for the next panel number.
7. Pressing < will return the display to the panel number prompt.
8. Press < to exit the network responses menu.
24.29How To Edit The Panel’s Network Special Function Responses.
1. Enter the engineers menu.
2. Select 3: Network Setup; 2: Edit Responses
NETWORK RESPONSES
1=DISPLAY,2=PRINTER
3=MEMORY, 4=CONTROLS
5=SPECIAL <=EXIT
3. Select 5: Special
SPECIAL RESPONSES
PANEL? 001
>=ENTER, <=EXIT
4. Enter panel number.
ACCEPT FROM PAN.001
1=DAY/NIGHT MODE-1
2=SOUNDER EN/DIS-1
1-2=CHG.,>=NXT,<=END
5. Pressing 1 or 2 will toggle the value opposite the corresponding function type
between values 0, 1. (1 = day/night mode, 2 = sounder disablement) These values
have the following meaning:-
0 = ignore changes in this category.
1= accept changes in this category.
6. Pressing > will display the values for the next panel number.
7. Pressing < will return the display to the panel number prompt.
8. Press < to exit the network responses menu.
24.30How To Print The Panel’s Network Display Responses.
1. Enter the engineers menu.