APPENDIX E - Premier AL Mechanical And Environmental Specification
Mechanical Specification
Size: Height:
Width:
Depth:
480mm
410mm
160mm including lock and indented holes
Weight excluding batteries:
15kg
Environmental Specification
Operating temperature:
-5ºC to 40ºC
Operating humidity:
5% to 95%
Mains Input Specification
Voltage:
230V AC +10%/-15%
Maximum Input Power:
320VA
Protection:
T3.15A anti-surge sand filled fuse
Cable requirements:
Minimum of 1mm
2
copper controlled by a 5A
fuse.
Power Supply Output Specification
28V output:
25-28V
@
4A
mains
on
21-27V @ 4A mains failed
28V output protection:
Electronic current limiting
5V output:
4.7-5.4V @ 3A
5V output protection:
Electronic current limiting
Common fault output:
Open collector output labelled CF
Mains failed fault output:
Open collector output labelled MF
Battery Specification
Battery charger output:
Temperature compensated float charger 27.4V
±
0.1V @20
°
C; maximum current 1.5A (limited
if 28V load greater than 3.5A).
Maximum battery load:
5A
Battery type:
2 off 12V 12Ah sealed lead acid standby
battery
Battery size:
151mm x 98mm x 97.5mm
Battery circuit protection:
5A fast blow glass fuse
Mains failed fault battery current:
1 Loop panel:
2 Loop panel:
3 Loop panel:
4 Loop panel:
145mA
170mA
195mA
220mA
Mains failed alarm battery current:
1 Loop panel: 260mA
Page 106 of 111
02/10/03