Written by: A.C. Amended by GG
Checked by: JBJ
Document Number: USDISC Rev.: 3
Page 25 of 47
19/07/2004
6.18 How To Enable And Disable A Zone Of Devices (Stand-Alone
Panel)
1. Enter the disablement menu as described in section 1.1.
EN/DIS:1=POINTS
2=ZONES, 3=PRINTER
4=SOUNDERS 5=INPUTS
6=OUTPUTS, <=EXIT
2. Press 2. The following screen will be displayed:
ENABLE/DISABLE ZONE
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
3. To disable a single zone press 1. The following screen will be displayed:
SINGLE ZONE EN/DIS
ZONE? 01
>=ENTER, <=BACK/EXIT
4. Enter the zone number and press enter to continue. The next screen displays the
current zone disablement status. The example below shows zone 31 is enabled
with the option to disable.
SINGLE ZONE EN/DIS
ZONE 31 ENABLED
1=DISABLE ZONE
SELECT 1, <=EXIT
5. Press 1 to toggle the zone disablement status. If the selected zone is valid (i.e. is
allocated to at least one point) then zone will be disabled, and the display will update
to show the new status.
SINGLE ZONE EN/DIS
ZONE 31 DISABLED
1=ENABLE ZONE
SELECT 1, <=EXIT
6. Press escape to return to the previous page:
ENABLE/DISABLE ZONE
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
7. Press escape to exit the menu one level at a time.
6.19 How To Enable And Disable A Zone Of Devices (Network Panel)
1. Enter the disablement menu as described in section 1.1.