Written by: A.C. Amended by GG
Checked by: JBJ
Document Number: USDISC Rev.: 3
Page 28 of 47
19/07/2004
EN/DIS:1=POINTS
2=ZONES, 3=PRINTER
4=SOUNDERS 5=INPUTS
6=OUTPUTS, <=EXIT
2. Press 2. The following screen will be displayed:
ENABLE/DISABLE ZONE
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
3. To disable a range of zones press 2. The following screen will be displayed:
RANGE ZONES EN/DIS
PANEL? 001
>=ENTER, <=BACK/EXIT
4. Enter the panel number and press enter to continue.
PAN001 ZONES EN/DIS
ZONE? 01
>=ENTER, <=BACK/EXIT
5. Enter the first zone number and press enter to continue.
PAN001 ZONES EN/DIS
ZONES 11 TO 11
>=ENTER, <=BACK/EXIT
6. Enter the number of the second zone and press enter.
PAN001 ZONES EN/DIS
ZONES 11 TO 12
1=ENABLE, 2=DISABLE
SELECT 1..2, <=EXIT
7. Choose the option required:
i) To enable the range of points displayed press 1
ii) To disable the range of points press 2
iii) To exit without making any changes press escape
If the local panel number was entered then the appropriate local zones that have
devices allocated will be enabled/disabled.
If another panel number was entered then a suitable command will be sent via the
network to the appropriate panel.