The zone and group based events can occur on any device, or devices within the
specified zone or group:
•
Fire in a zone or group, output cleared on silence alarms:
The output is operated if a fire condition is active in the specified group or
zone. When the panel alarms are silenced by the user the output is cleared
•
Fire in a zone or group, output cleared on reset:
The output is operated if a fire condition is active in the specified group or
zone. When the panel is reset by the user the output is cleared
•
Any two fires in a zone or group, output cleared on silence alarms:
The output is operated if any two fire conditions are active in the specified
group or zone. When the panel alarms are silenced by the user the output is
cleared
•
Any two fires in a zone or group, output cleared on reset:
The output is operated if any two fire conditions are active in the specified
group or zone. When the panel is reset by the user the output is cleared
•
Alert in a zone or group, output cleared on cause clear:
The output is operated if any alert condition is active in the specified group or
zone. When the panel is reset by the user, or the alert condition is removed, the
output is cleared
•
Fault in a zone or group, output cleared on cause clear:
The output is operated if any fault condition is active in the specified group or
zone. When the panel is reset by the user, or the fault condition is removed, the
output is cleared
•
Indication in a zone or group, output cleared on cause clear:
The output is operated when an indication only event is active in the specified
group or zone. When the panel is reset by the user, or the indication condition
is removed, the output is cleared.
Note: A group contains device points in the same way as a zone, but the group is
used solely for cause/effect programming.
16.9Premier AL Global Repeater Panel
The Premier AL [panel] repeaters duplicate the panel indications and user controls at
a location remote from the main panel. Up to 14 repeaters can be connected to a single
panel using an RS485 serial connection.
Note: The menu functions are not available at panel repeaters.
16.10Panel Input Output Expansion Boards
The Premier panels can be expanded by the use of the A1535 and A1536 expansion
boards. These are located in an expanded cabinet that has an extra compartment
dedicated to the expansion boards.
The A1535 provides 8 fully monitored inputs and 8 outputs. Two types of A1535 are
available, one with open collector outputs and one with change over relay contacts.
The A1536 provides 8 non-monitored inputs and 8 fully monitored alarm circuits.
All expansion board inputs and outputs can be configured as part of the panel
cause/effect using the menu functions or the PC configuration software. For full
details of the expansion boards see documents A1535 Application, Installation and
Page 34 of 111
02/10/03