The zone and group based events can occur on any device, or devices within the 

specified zone or group:

Fire in a zone or group, output cleared on silence alarms: 

The output is operated if a fire condition is active in the specified group or 
zone. When the panel alarms are silenced by the user the output is cleared

Fire in a zone or group, output cleared on reset: 

The output is operated if a fire condition is active in the specified group or 
zone. When the panel is reset by the user the output is cleared

Any two fires in a zone or group, output cleared on silence alarms: 

The output is operated if any two fire conditions are active in the specified 
group or zone. When the panel alarms are silenced by the user the output is 
cleared

Any two fires in a zone or group, output cleared on reset: 

The output is operated if any two fire conditions are active in the specified 
group or zone. When the panel is reset by the user the output is cleared

Alert in a zone or group, output cleared on cause clear: 

The output is operated if any alert condition is active in the specified group or 
zone. When the panel is reset by the user, or the alert condition is removed, the 
output is cleared

Fault in a zone or group, output cleared on cause clear: 

The output is operated if any fault condition is active in the specified group or 
zone. When the panel is reset by the user, or the fault condition is removed, the 
output is cleared

Indication in a zone or group, output cleared on cause clear: 

The output is operated when an indication only event is active in the specified 
group or zone. When the panel is reset by the user, or the indication condition 
is removed, the output is cleared.

Note: A group contains device points in the same way as a zone, but the group is  
used solely for cause/effect programming.

16.9Premier AL Global Repeater Panel

The Premier AL [panel] repeaters duplicate the panel indications and user controls at 

a location remote from the main panel. Up to 14 repeaters can be connected to a single 

panel using an RS485 serial connection. 

Note: The menu functions are not available at panel repeaters.

16.10Panel Input Output Expansion Boards

The Premier panels can be expanded by the use of the A1535 and A1536 expansion 

boards. These are located in an expanded cabinet that has an extra compartment 

dedicated to the expansion boards.

The A1535 provides 8 fully monitored inputs and 8 outputs. Two types of A1535 are 

available, one with open collector outputs and one with change over relay contacts. 

The A1536 provides 8 non-monitored inputs and 8 fully monitored alarm circuits.

All expansion board inputs and outputs can be configured as part of the panel 

cause/effect using the menu functions or the PC configuration software. For full 

details of the expansion boards see documents A1535 Application, Installation and 

Page 34 of 111

02/10/03

Содержание Premier AL

Страница 1: ...MIER AL GLOABAL NETWORK REPEATER MANUAL see also ZETA ALARMS PREMIER AL GLOBAL NETWORK REPEATER PDF FOR USER INSTRUCTIONS AND GUIDE INSTALLATION COMMISSIONING AND MAINTENANCE with USER INSTRUCTIONS AN...

Страница 2: ......

Страница 3: ...oard WARNING DO NOT PLUG IN OUT REPEATER I OBOARD CARD WHILE PREMIER AL IS POWERED ON TURN OFF THE MAINS POWER ALWAYS WHEN REMOVING OR PLUGGING IN REPEATER I OBOARD CARDS 9 6 1 7 A1620 Network Interfa...

Страница 4: ...Order Codes Descriptions 28 15 Overview Of User Functions 29 15 1 Change Time And Date 29 15 2 Delay Of Operation Of Outputs 29 15 3 Adjustable Sensitivity Modes 29 15 4 Enabling And Disabling Of Func...

Страница 5: ...imed Sensitivity Mode 50 23 7 How To Enable Off Sensitivity Mode 51 23 8 How To Enable And Disable A Single Point Stand Alone Panel 52 23 9 How To Enable And Disable A Single Point Network Panel 53 23...

Страница 6: ...Of Devices To A Group 91 24 14 How To Edit Loop Output Cause And Effect 92 24 15 How To Print Loop Output Cause And Effect 92 24 16 How To Change The Remote Evacuate Mode 93 24 17 How To Edit The Pan...

Страница 7: ...5 APPENDIX E Premier AL Mechanical And Environmental Specification 106 APPENDIX F Premier AL Global Network Repeater MechanicalAnd Environmental Specification 108 APPENDIX G Premier AL Input and Outpu...

Страница 8: ...layout 26 Figure 8 Power supply layout 27 Figure 9 Auxiliary fire contact connection details 37 Figure 10 Auxiliary fault contact connection details 38 Figure 11 Monitored input circuit configuration...

Страница 9: ...oad calculation spreadsheet is recommended Field device manuals 2 Define the device location texts and panel cause and effect The use of the panel planning chart and cause effect charts are recommende...

Страница 10: ...shown in Figure 1 One loop card is fitted for each loop that is connected to the panel The Premier AL drives a maximum of four loops of devices Figure 1 Premier AL panel main components 6 1 1XP 150W 3...

Страница 11: ...O NOT PLUG IN OUT REPEATER I OBOARD CARD WHILE PREMIER AL IS POWERED ON TURN OFF THE MAINS POWER ALWAYS WHEN REMOVING OR PLUGGING IN REPEATER I OBOARD CARDS This optional plug in board provides an RS4...

Страница 12: ...all the field terminations an internal interface for up one plug in loop card connections for an A1619 interface for expansion I O communication connections for an A1620 Network card and connections...

Страница 13: ...ffect editor Panel Repeaters Up to 14 panel repeaters may be connected over 1200m RS485 link User definable access code Changed using PC cause effect editor User definable text for panel name and devi...

Страница 14: ...Local or via a remote network panel View disablements Local only function Printer Local only function Event Log Records last 200 events Can be configured to record network responses Test functions Zo...

Страница 15: ...ogrammable remote panel output cause effect 6 The ability to download site specific data from a computer text zone information and cause effect 7 The ability to upload the data from the panel Site spe...

Страница 16: ...heavy take great care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used WARNING Do not attempt to remove battery lid or tamper with the battery internal w...

Страница 17: ...5 Carefully put the door on one side and replace the hinge pin in the back box 6 Remove the earth strap connecting the back box and chassis by removing the nut and washer on the chassis Carefully note...

Страница 18: ...reconnected correctly Do not connect the field wiring at this stage 23 Remove the two screws securing each battery clamp and place the battery clamps to one side 24 Place the left battery into the bot...

Страница 19: ...A REPEATER DISPLAY FIRST A1575 REPEATER DISPLAY OR LOCAL PSE USE PANEL SUPPLY A1619 INTERFACE BOARD FITTED TO LEFT POSITION ON A1579 TO DRIVE REPEATERS SUBSEQUENT A1575 Figure 3 Panel Repeater connect...

Страница 20: ...NEXT PANEL Figure 4 Network connection diagram 4 Set the network node address on the A1620 NETWORK ADDRESS switch as shown Table 1 It should be noted that any number of panels can be configured as ad...

Страница 21: ...nce with Premier AL wiring recommendations BS5839 part 1 and current IEE wiring regulations ii All field cables are glanded into the control panel cabinet iii Detector bases are terminated but detecto...

Страница 22: ...The procedure is to test that the panels are communicating and configured correctly 1 Check that each panel displays different types of events from every other appropriate panel This confirms that the...

Страница 23: ...ch Check that all sounders connected to the alarm circuit operate 3 Press Silence Alarms and Reset Repeat steps 1 to 3 for the second and any subsequent alarm circuits 9 5 2Commissioning Loops 1 Ensur...

Страница 24: ...the corresponding loop 9 5 3Commissioning a Network System 1 Ensure the network card is fitted in each panel and that the network cabling is correctly installed 2 Ensure that each panel has been commi...

Страница 25: ...10 Premier AL Motherboard Features Figure 5 illustrates the Premier motherboard features referred to elsewhere in the documentation Page 23 of 111 02 10 03...

Страница 26: ...nt type recommended by the manufacturer Dispose of used batteries according to the manufacturer s instructions Only trained service personnel should replace this battery Page 24 of 111 02 10 03 Fit li...

Страница 27: ...9V CHARGE Charger fault EARTH Earth fault disabled 5 8V 5V supply low MAIN Input from SMPS out of tolerance THERM Thermistor fault PSU OK Power supply healthy switches off for 1s every 30s during batt...

Страница 28: ...A1638 Motherboard layout Lithium battery caution danger of explosion if battery is incorrectly replaced Replace only with CR1620 3V or equivalent type recommended by the manufacturer Dispose of used b...

Страница 29: ...MON EARTH CAP BATT FAULT FAULT O C P 0V 24V SUPPLY EARTH FAULT MAINS FAILED NO CHARGE HEALTHY AC AC CHARGER ADJUST 27 5V 24V ADJUST ENABLE LINK VR2 VR1 LK1 LK2 FS1 Connections to motherboard Red 24V B...

Страница 30: ...ive Beam Detector 100 meters 37 150 FECO2000 Fyreye Carbon Monoxide Detector 47 110 FE 50 AD Fyreye Plus Aspiration Detector 80 050 FE CB Fyreye Common Base 80 080 FE ARB Fyreye Relay Base 80 090 FE I...

Страница 31: ...ill also be delayed 15 3Adjustable Sensitivity Modes The Premier AL panels can be configured to automatically adjust device sensitivity according to the time of day Three different sensitivity levels...

Страница 32: ...sed Events System events are prioritised to clarify the display of information by the system The events are classified in the following levels in decreasing order of priority Fire Alert Fault If event...

Страница 33: ...to the write enable position to allow any changes If the switch is inadvertently left in the enable position when the changes are complete the panel indicates a fault condition 16 5Point Configuration...

Страница 34: ...med by the engineer according to site specific requirements The default cause and effect is shown in Table 2 Table 2 Default command output bits Device type Output command bit operation Addressable So...

Страница 35: ...t output cleared on cause clear The output is operated if any alert condition is active on the panel When the panel is reset by the user or the alert condition is removed the output is cleared Common...

Страница 36: ...ne When the panel is reset by the user or the fault condition is removed the output is cleared Indication in a zone or group output cleared on cause clear The output is operated when an indication onl...

Страница 37: ...cannot be accessed through the menu 16 12Class change Modes The operation of the class change input may be selected to operate ouput bit 0 steady or 1 pulsed of any loop sounder controllers 17 Power S...

Страница 38: ...y 1 5 to derive the current drawn from the battery 5 Calculate the maximum load on the alarm circuits in mA in an alarm condition Enter this value as Ialarms and enter this figure in the table 6 Calcu...

Страница 39: ...volt free auxiliary relay contacts must not be used to directly switch any voltage which exceeds 30VDC Auxiliary changeover contacts are provided which operate on fire and fault conditions There are t...

Страница 40: ...witch contact Two switches are shown in Figure 11 although there is no limit to the number of switches 680R 680R SWITCH SWITCH END OF LINE 3k9 INPUT CIRCUIT INPUT CIRCUIT Figure 11 Monitored input cir...

Страница 41: ...gure 13 Alarm circuit configuration The voltage drop on each alarm circuit should be calculated to ensure that the minimum voltage at the end of each circuit exceeds the minimum required by each sound...

Страница 42: ...rop for each loop perform the following steps 1 Calculate the maximum alarm load on the loop in mA Enter this value as Iloop 2 Count the total number of isolators Enter this value as Niso 3 Calculate...

Страница 43: ...a zone number This also applies to other types of event 1 001 Z01 OPT FIRE DEVICE LOCATION The sounder circuits are operated System outputs are operated according to the panel programming The event is...

Страница 44: ...displayed in the same way as for fire events During an alert condition the display of events of a lower priority is suppressed To view these events refer to section 23 27 21 2 1User Actions Switch th...

Страница 45: ...g a fault condition the display of events of a lower priority is suppressed To view these events refer to section 23 27 21 3 1User Actions Switch the ACCESS CONTROLS keyswitch to the ON position to en...

Страница 46: ...21 4The Maintenance Condition This facility is not used on the Fyreye detectors and is for future use Page 44 of 111 02 10 03...

Страница 47: ...tely 22 1 2Service Engineer Actions Open the outer panel door Operate the SYSTEM FAULT RESET switch on the motherboard This is identified in Figure 5 Operate the PROCESSOR RESET switch on the motherbo...

Страница 48: ...DE DELAY 1 2 3 4 5 6 Page 46 of 111 02 10 03 Zonal fire red and fault yellow indications Pulse to indicate a non silenced event continuous to indicate an event has been silenced Zonal fire red and fau...

Страница 49: ...lete items and escape from menus Enters text in the access menus User controls Only override delay is available without operating the access controls keyswitch User indications 20 character by 4 line...

Страница 50: ...ed For example when setting the time the current time is displayed The cursor will underline the first digit 2 Press MENU UP or MENU DOWN to increment or decrement the digit 3 When the digit is correc...

Страница 51: ...enter to save the value and return to the user menu screen 23 3How To Enable And Disable The Panel Delay 1 Enter the user menu as described in section 23 2 Press 2 to select option 2 The following scr...

Страница 52: ...me 23 5How To Enable Night Sensitivity Mode 1 Enter the user menu as described in section 23 2 Press 2 to select option The following screen will be displayed PANEL MODES 1 PANEL DELAY 2 DAY NIGHT SEL...

Страница 53: ...XIT 5 Selecting the Timer option enables the active trip levels and sensitivity codes depend upon the day of the week and the time 23 7How To Enable Off Sensitivity Mode 1 Enter the user menu as descr...

Страница 54: ...ollowing screen will be displayed EN DIS 1 POINTS 2 ZONES 3 PRINTER 4 SOUNDERS 5 INPUTS SELECT 1 5 EXIT 4 Press 1 The following screen will be displayed ENABLE DISABLE POINT 1 SINGLE 2 RANGE 3 VIEW 4...

Страница 55: ...00 ZNS MENU EXIT This example shows no zones 3 points no inputs all sounders and the printer are disabled These values only relate to the status of the local panel 3 Press enter to continue The follow...

Страница 56: ...E 2 RANGE 3 VIEW 4 ENABLE ALL SELECT 1 4 EXIT Press escape to exit the menu one level at a time 23 10How To Enable And Disable A Range Of Points Stand Alone Panel 1 Enter the user menu as described in...

Страница 57: ...t and press enter 1 015 030 EN DIS 1 ENABLE POINTS 2 DISABLE POINTS SELECT 1 2 EXIT 9 Choose the option required i To enable the range of points displayed press 1 ii To disable the range of points pre...

Страница 58: ...3 PRINTER 4 SOUNDERS 5 INPUTS SELECT 1 5 EXIT 4 Press 1 The following screen will be displayed ENABLE DISABLE POINT 1 SINGLE 2 RANGE 3 VIEW 4 ENABLE ALL SELECT 1 4 EXIT To disable a range of points pr...

Страница 59: ...entered then a suitable command will be sent via the network to the appropriate panel The screen will display the previous page ENABLE DISABLE POINT 1 SINGLE 2 RANGE 3 VIEW 4 ENABLE ALL SELECT 1 4 EX...

Страница 60: ...for a network panel DISABLED POINTS 5 1 1 5 9 22 30 125 5 2 55 70 1 BACK 2 NEXT EXIT Where the indicated disablements are for panel 5 6 Press 1 and 2 to scroll through the screens displaying the disab...

Страница 61: ...NTS ENABLED EXIT 6 Press escape to exit the menu one level at a time 23 14How To Enable And Disable A Zone Of Devices Stand Alone Panel 1 Enter the user menu as described in section 23 2 Press 3 to se...

Страница 62: ...ONE 1 SINGLE 2 RANGE 3 VIEW SELECT 1 3 EXIT 8 Press escape to exit the menu one level at a time 23 15How To Enable And Disable A Zone Of Devices Network Panel 1 Enter the user menu as described in sec...

Страница 63: ...us The example below shows zone 31 is enabled with the option to disable PAN001 ZONE EN DIS ZONE 31 ENABLED 1 DISABLE ZONE SELECT 1 EXIT 8 Press 1 to toggle the zone disablement status The screen will...

Страница 64: ...NES EN DIS ZONE 01 ENTER BACK EXIT 6 Enter the first zone number and press enter to continue RANGE ZONES EN DIS ZONES 11 TO 11 ENTER BACK EXIT 7 Enter the number of the second zone and press enter RAN...

Страница 65: ...cal panel 3 Press enter to continue The following screen will be displayed EN DIS 1 POINTS 2 ZONES 3 PRINTER 4 SOUNDERS 5 INPUT SELECT 1 5 EXIT 4 Press 2 The following screen will be displayed ENABLE...

Страница 66: ...ISABLE ZONE 1 SINGLE 2 RANGE 3 VIEW SELECT 1 3 EXIT 9 Press escape to exit the menu one level at a time 23 18How To View Disabled Zones 1 Enter the user menu as described in section 23 2 Press 3 to se...

Страница 67: ...wing messages appears DISABLED ZONES NO MORE DISABLEMENTS 1 BACK EXIT 7 Press escape to exit the menu one level at a time 23 19How To Enable And Disable The Local Printer 1 Enter the user menu as desc...

Страница 68: ...And Disable All Sounding Devices 1 Enter the user menu as described in section 23 2 Press 3 to select option 3 The screen will display the current disabled devices DISABLEMENT SUMMARY 0003 POINTS 000...

Страница 69: ...reen will display the current disabled devices DISABLEMENT SUMMARY 0003 POINTS 000 INPS SOUNDERS PRINTER 00 ZNS MENU EXIT This example shows no zones 3 points no inputs all sounders and the printer ar...

Страница 70: ...he current disabled devices DISABLEMENT SUMMARY 0003 POINTS 000 INPS SOUNDERS PRINTER 00 ZNS MENU EXIT This example shows no zones 3 points no inputs all sounders and the printer are disabled These va...

Страница 71: ...IT 9 Press escape to exit the menu one level at a time 23 23How To Enable And Disable A Range Of Expansion Board Inputs Stand Alone Panel 1 Enter the user menu as described in section 23 2 Press 3 to...

Страница 72: ...nputs press 2 iii To exit without making any changes press escape The screen will display the previous page INPUT DISABLEMENT 1 SINGLE 2 RANGE 3 VIEW SELECT 1 3 EXIT 9 Press escape to exit the menu on...

Страница 73: ...CK EXIT 7 Enter the first input number and press enter to continue PAN001 INPUTS EN DIS INPUTS 001 TO 001 ENTER BACK EXIT 8 Enter the number of the second zone and press enter PAN001 INPUTS EN DIS INP...

Страница 74: ...l sounders and the printer are disabled These values only relate to the status of the local panel 3 Press enter to continue The following screen will be displayed EN DIS 1 POINTS 2 ZONES 3 PRINTER 4 S...

Страница 75: ...will be displayed 1 VIEW EVENT LOG 2 VIEW SUPPRESSED EVENTS SELECT 1 2 EXIT 3 Press 1 to view the event log A screen showing the first event in the log will be displayed 20 05 96 13 24 08 1 007 Z02 BG...

Страница 76: ...r point 1 011 1 BACK 2 NEXT EXIT 5 Scroll through the events by pressing 1 or 2 When the last event is reached a screen will display a message similar to the following NO MORE SUPPRESSED ALERTS 1 BACK...

Страница 77: ...In the enabled mode the panel will respond to all device events If a device is operated manually or a self test changes the device condition the panel will respond to the event If a point status is vi...

Страница 78: ...t log with the description TEST instead of FIRE No alarms or relays will be operated but the led on the point in fire will illuminate for ten seconds Any fire events from zones not in test mode will c...

Страница 79: ...t mode is active POINT TEST ACTIVE IN ZONES 1 1 CANCEL TEST EXIT In addition the TEST LED will be illuminated When the test is complete press 1 to cancel the test mode 23 31How To Test Sounding Device...

Страница 80: ...QUEUE 2 PRINT EVENT LOG 3 PRINT DISABLEMENTS SELECT 1 3 EXIT 3 Press 1 to clear the print queue The following screen will confirm the operation PRINT QUEUE CLEARED EXIT 4 Press escape to exit to the p...

Страница 81: ...scribed in section 23 2 Press 6 The following screen will be displayed 1 CLEAR PRINT QUEUE 2 PRINT EVENT LOG 3 PRINT DISABLEMENTS SELECT 1 3 EXIT 3 Press 3 to print the disablements If the printer is...

Страница 82: ...d 1 USER MENU ENTER ACCESS CODE FOR ENGINEER MENU 0000 3 Enter the engineer s access code 8812 as described in section 23 1 Press to enter the engineer s access menu ENGINEER ACCESS MENU 1 USER FUNCTI...

Страница 83: ...curs then the changes to the site specific data WILL NOT BE SAVED This can occur unintentionally if the escape switch is pressed several times in succession to exit from a site specific data editing m...

Страница 84: ...is correct The delay menu will be displayed 1 DELAY ENABLE 2 DELAY TIMES 3 DELAY DURATION SELECT 1 3 EXIT 10 Press 3 to set the delay duration The following screen will be displayed DELAY IS 01 MINUTE...

Страница 85: ...ts report will be generated This indicates the types of devices on the loop LOOP 1 009 MCP 082 SENSORS 012 MODULES SAVE EXIT Press enter to save the configuration data or escape to exit without overwr...

Страница 86: ...TER BACK EXIT 4 Enter the loop number and press enter If the printer is disabled at this can be overridden by pressing 1 PRINT LOOP CONTENT PRINTER IS DISABLED 1 IGNORE DISABLEMENT EXIT 5 The followin...

Страница 87: ...ivity For example changing the sensitivity of a point whilst the panel is in day mode does not affect the sensitivity values of that point for the default or night mode sensitivity 24 8How To Edit The...

Страница 88: ...dited then enter the same number as the first device EDIT ZONE 07 LOOP 01 POINTS 015 TO 022 1 ADD 2 REM EXIT 9 Press 1 to add the devices to the zone or 2 to remove the devices from the zone If no cha...

Страница 89: ...ng message is displayed PRINTING POINT ZONES CANCEL Press escape to cancel the report at any time 6 When the report is complete the following message is displayed PRINTING POINT ZONES COMPLETE EXIT 7...

Страница 90: ...to move through the list of points in the zone indicated When the last page has been displayed The following screen will be displayed VIEW ZONE 13 NO MORE POINTS 1 BACK EXIT 8 Press escape to exit the...

Страница 91: ...Enter the first device in a range to be added or removed from the group This example shows device 15 EDIT GROUP 068 LOOP 01 POINTS 015 TO 015 ENTER BACK 8 Enter the last device to be added or removed...

Страница 92: ...T 4 Press 3 to view the allocation of points to a group VIEW GROUPS GROUP 033 ENTER BACK EXIT 5 Enter the group to be viewed and press enter While the report is generated the following message is disp...

Страница 93: ...NT GROUPS 3 VIEW POINT GROUPS SELECT 1 3 EXIT 4 Press 2 to print the point group allocation If the printer is disabled press 1 to override the disablement when prompted to do so The report will be pre...

Страница 94: ...Press 4 to add more causes The display is as follows CAUSES FOR 1 001 BT0 1 GROUP CAUSE 2 COMMON CAUSE SELECT 1 2 EXIT 5 Either i Select option 1 to add a group cause Enter the group number ii Select...

Страница 95: ...keyboard 5 Press return on the keyboard or to store the text Alternatively press escape on the keyboard or on the keypad to retain the existing text 24 18How To Edit Point Location Text 1 Plug a Cherr...

Страница 96: ...e address of the board to be configured using the menu up and down keys 2 Press to enter the board number or press to escape without changing the board configuration If the board number is entered the...

Страница 97: ...xpansion I O board configuration enter the engineers menu and select 1 Panel set up 2 Input output set up 3 Panel output c e 1 Input group allocation 1 Edit I P groups 1 The following screen will be d...

Страница 98: ...will be active continuously If channel 1 is active the output will pulse for 1s on 1s off If both channel 0 and channel 1 are active the output will be continuous The expansion I O cause effect is edi...

Страница 99: ...enter the device specification accordingly 3 When printing is complete the following message will appear PRINTING PANEL OUTPUT C E COMPLETE EXIT 4 Press to exit the remote output cause effect menu 24...

Страница 100: ...ng 0 ignore events in this category 1 display events with just the panel name on line 2 2 display events with actual user text on line 2 Pressing will display the values for the next panel number Pres...

Страница 101: ...sponses 1 Enter the engineers menu 2 Select 3 Network Setup 2 Edit Responses NETWORK RESPONSES 1 DISPLAY 2 PRINTER 3 MEMORY 4 CONTROLS 5 SPECIAL EXIT 3 Select 5 Special SPECIAL RESPONSES PANEL 001 ENT...

Страница 102: ...ss Change Modes The panel can drive either channel 0 steady or channel 1 pulsing of loop sounders in response to the class change input 24 31 1To change the output bits enter the engineers menu and se...

Страница 103: ...cted the siting of manual call points or sounders Any defects should be recorded in the logbook and reported to the responsible person and action should be taken to correct it 25 2Annual Inspection Th...

Страница 104: ...2 ALERT 2 POINT SENSITIVITY 1 PRINT DRIFT 2 PRINT DATE 3 LED 4 RAPID COMPENSATION 3 DISCOVERY 1 LOOP CONFIGURATION 1 EDIT POINT ZONES 2 PRINT POINT ZONES 3 VIEW POINT ZONES 2 ZONE ALLOCATION 1 EDIT P...

Страница 105: ...Line resistor ESD Electro Static Discharge I O Input output LCD Liquid Crystal Display Alphanumeric display used for textual information LED Light Emitting Diode Display indicator MCP Manual Call Poin...

Страница 106: ...nt on a panel does not cause an action on any other panel c f network cause effect MCP Manual Call Point also know as BGU Network cause effect Cause effect where an event on one panel causes an action...

Страница 107: ...FLT Data Fault the analogue value reported by the device is not valid DADDR Double Address two or more devices exist with the same address FUSE FAILED Auxiliary power supply fuse failed LINE FAULT Ope...

Страница 108: ...ed 28V output protection Electronic current limiting 5V output 4 7 5 4V 3A 5V output protection Electronic current limiting Common fault output Open collector output labelled CF Mains failed fault out...

Страница 109: ...2 Loop panel 3 Loop panel 4 Loop panel 285mA 310mA 335mA Page 107 of 111 02 10 03...

Страница 110: ...f 1mm2 copper controlled by a 5A fuse Power Supply Output Specification 24V output 24V 0 5V 3A mains on 21 26V 3A mains failed 24V output protection Electronic current limiting Common fault output Ope...

Страница 111: ...ve O2 Loop out ve I2 Loop return ve I2 Loop return ve Loop 3 Terminals Premier AL only O3 Loop out ve O3 Loop out ve I3 Loop return ve I3 Loop return ve Loop 4 Terminals Premier AL O4 Loop out ve O4 L...

Страница 112: ...oltage at end of line must be above sounding device minimum operating voltage Premier AL Repeater Panel Output Specification Number of repeaters 1 to 14 Maximum repeater cable length 2000m Communicati...

Страница 113: ...of nodes 1 to 15 Maximum network cable length 5000m Communication protocol RS485 serial data 9600 baud Protection Electronic current limited Cable Type Single pair RS485 shielded cable see below RS485...

Страница 114: ...rinter Functions 10 5 User Controls and Indications 11 6 User Functions 13 6 1 How To Enter Numbers 13 6 2 How To Set The Time And Date 13 6 3 How To Enable And Disable The Panel Delay 14 6 4 How To E...

Страница 115: ...And Disable A Range Of Expansion Board Inputs Network Panel 33 6 29 How To View Disabled Expansion Board Inputs 34 6 30 How To Enable And Disable All Non Sounder Devices 35 6 31 How To View The Event...

Страница 116: ...he COMMON FIRE and relevant zone LEDs pulse The internal buzzer sounds intermittently if the device is allocated to a zone The top two lines of the LCD display details of the event 1 001 Z01 OPT FIRE...

Страница 117: ...if a printer is fitted Subsequent events will be displayed in the same way as for fire events During an alert condition the display of events of a lower priority is suppressed To view these events re...

Страница 118: ...events of a lower priority is suppressed To view these events refer to section 6 32 User Actions Switch the ACCESS CONTROLS keyswitch to the ON position to enable the controls Press the SILENCE BUZZE...

Страница 119: ...ondition they were in when the fault occurred Some sounders may thus remain active Warning The system is completely inactive User Actions Determine the area affected by the fault and decide whether sp...

Страница 120: ...iew Of User Functions This section describes an overview of the functions available to the end user 4 1 Change Time And Date The user can manually set the time and date although this should not normal...

Страница 121: ...night modes according to the time The day and night times are defined through the PC cause effect editor A separate time can be defined for each day of the week Switching OFF the day night sensitivity...

Страница 122: ...formation by the system The events are classified in to the following levels in decreasing order of priority Fire Alert Fault Indication If events at more than one level exist on the panel only events...

Страница 123: ...AND FAULT INDICATION 5 6 7 8 9 10 32 31 30 27 28 29 12 11 13 15 14 16 CONTROLS ACCESS 6 5 4 3 2 1 Switch to 1 to enable controls enter level 2 Override delay operates with switch in either position U...

Страница 124: ...indications Fire conditions must be silenced first Tests all indications and internal buzzer Used within access menu to delete items and escape from menus Enters text in the access menus Operates all...

Страница 125: ...ly The timeout period depends on the function selected and is between 1 and 15 minutes 6 1 How To Enter Numbers All menu selections are made using direct key access using keys 1 to 6 Entry of digits i...

Страница 126: ...NTER VALUE BACK EXIT 6 Change the time as required and press enter to save the value and return to the user menu screen 6 3 How To Enable And Disable The Panel Delay 1 Enter the user menu as described...

Страница 127: ...iate trip levels and sensitivity codes to the Day Time value regardless of the time 6 5 How To Enable Night Sensitivity Mode 1 Enter the user menu as described in section 6 2 Press 2 to select option...

Страница 128: ...GHT 3 TIMER 4 OFF EXIT 5 Selecting the Timer option enables the active trip levels and sensitivity codes depend upon the day of the week and the time 6 7 How To Enable Off Sensitivity Mode 1 Enter the...

Страница 129: ...ENABLED 1 NEXT MENU EXIT DISABLEMENT SUMMARY BUZZER ENABLED 1 NEXT MENU EXIT This example shows no zones 3 points no inputs all sounders and the printer are disabled while outputs and the buzzer are...

Страница 130: ...ate to show the new status SINGLE POINT EN DIS 1 023 DISABLED 1 ENABLE POINT SELECT 1 EXIT 7 Press escape to return to the previous page ENABLE DISABLE POINT 1 SINGLE 2 RANGE 3 VIEW 4 ENABLE ALL SELEC...

Страница 131: ...point disablement status Either the local point will be disabled or a message will be sent to the network and the screen will be updated to show the new status PAN001 POINT EN DIS 1 023 DISABLED 1 EN...

Страница 132: ...T 1 2 EXIT 7 Choose the option required i To enable the range of points displayed press 1 ii To disable the range of points press 2 iii To exit without making any changes press escape The screen will...

Страница 133: ...PAN001 POINTS EN DIS 1 015 030 1 ENABLE 2 DISABLE SELECT 1 2 EXIT 8 Choose the option required i To enable the range of points displayed press 1 ii To disable the range of points press 2 iii To exit...

Страница 134: ...for a stand alone panel DISABLED POINTS 1 1 5 9 22 30 125 2 55 70 1 BACK 2 NEXT EXIT or as follows for a network panel DISABLED POINTS 5 1 1 5 9 22 30 125 5 2 55 70 1 BACK 2 NEXT EXIT Where the indic...

Страница 135: ...el 1 Enter the disablement menu as described in section 1 1 EN DIS 1 POINTS 2 ZONES 3 PRINTER 4 SOUNDERS 5 INPUTS 6 OUTPUTS EXIT 2 Press 1 The following screen will be displayed ENABLE DISABLE POINT 1...

Страница 136: ...ne level at a time 6 17 How To Enable All Points At Selected Panel Network Panel 1 Enter the disablement menu as described in section 1 1 EN DIS 1 POINTS 2 ZONES 3 PRINTER 4 SOUNDERS 5 INPUTS 6 OUTPUT...

Страница 137: ...enter to continue The next screen displays the current zone disablement status The example below shows zone 31 is enabled with the option to disable SINGLE ZONE EN DIS ZONE 31 ENABLED 1 DISABLE ZONE...

Страница 138: ...ZONE EN DIS ZONE 31 ENABLED 1 DISABLE ZONE SELECT 1 EXIT 6 Press 1 to toggle the zone disablement status If the local panel is specified and the selected zone is valid i e has at least one point allo...

Страница 139: ...er the first zone number and press enter to continue RANGE ZONES EN DIS ZONES 11 TO 11 ENTER BACK EXIT 5 Enter the number of the second zone and press enter RANGE ZONES EN DIS ZONES 11 TO 12 1 ENABLE...

Страница 140: ...mber and press enter to continue PAN001 ZONES EN DIS ZONES 11 TO 11 ENTER BACK EXIT 6 Enter the number of the second zone and press enter PAN001 ZONES EN DIS ZONES 11 TO 12 1 ENABLE 2 DISABLE SELECT 1...

Страница 141: ...LED ZONES PREPARING REPORT PLEASE WAIT EXIT The report will be displayed as follows for a stand alone panel DISABLED ZONES 1 3 10 12 15 18 25 30 1 BACK 2 NEXT EXIT or will be displayed as follows for...

Страница 142: ...SOUNDERS 5 INPUTS 6 OUTPUTS EXIT 2 Press 4 The screen will display the current sounder disablement status This example shows the sounding devices are disabled SOUNDERS DISABLED 1 ENABLE SOUNDERS SELEC...

Страница 143: ...disable IDENTIFY INPUT INPUT 010 ENABLED 1 DISABLE INPUT SELECT 1 EXIT 5 Press 1 to toggle the input disablement status The screen will display the previous page INPUT DISABLEMENT 1 SINGLE 2 RANGE 3...

Страница 144: ...screen will display the previous page INPUT DISABLEMENT 1 SINGLE 2 RANGE 3 VIEW SELECT 1 3 EXIT 7 Press escape to exit the menu one level at a time 6 27 How To Enable And Disable A Range Of Expansion...

Страница 145: ...PUT DISABLEMENT 1 SINGLE 2 RANGE 3 VIEW SELECT 1 3 EXIT 7 Press escape to exit the menu one level at a time 6 28 How To Enable And Disable A Range Of Expansion Board Inputs Network Panel 1 Enter the d...

Страница 146: ...entered then the appropriate local inputs will be enabled disabled If another panel number was entered then a suitable command will be sent via the network to the appropriate panel The screen will di...

Страница 147: ...creens displaying the disabled devices When all the devices have been viewed the following messages appears DISABLED INPUTS NO MORE DISABLEMENTS 1 BACK EXIT 5 Press escape to exit the menu one level a...

Страница 148: ...the first event in the log will be displayed 20 05 96 13 24 08 1 007 Z02 BGU FIRE text for point 1 007 1 BACK 2 NEXT EXIT 4 Press 1 or 2 to scroll forwards or backwards through the event log The first...

Страница 149: ...o exit the menu one level at a time 6 33 How To View Suppressed Disablements 1 Enter the user menu as described in section 6 2 Press 4 to select option 4 The following screen will be displayed 1 VIEW...

Страница 150: ...viewed in the disabled mode then the panel will no longer respond to device events although any change in status will be displayed This is useful for testing the analogue devices using the self test...

Страница 151: ...or cause effect will be operated but the sounders may operate for ten seconds if the appropriate mode is selected The LED on the point in fire will illuminate for ten seconds Any fire events from othe...

Страница 152: ...In addition the TEST LED will be illuminated When the test is complete press 1 to cancel the test mode How To Test Sounding Devices Using One Person Test Mode In this test all of the alarms will sound...

Страница 153: ...EARED EXIT 4 Press escape to exit to the printer main menu 6 38 How To Print The Event Log 1 Enter the user menu as described in section 6 2 Press 6 The following screen will be displayed PRINTER MENU...

Страница 154: ...XIT 4 Press 1 to print the disablements If the printer is currently disabled a message will appear Press 1 to override the disablement PRINT DISABLEMENTS PRINTER IS DISABLED 1 IGNORE DISABLEMENT EXIT...

Страница 155: ...RINTER MENU 1 CLEAR PRINT QUEUE 2 PRINT EVENT LOG NEXT PAGE EXIT 3 Press enter The following screen will be displayed PRINTER MENU 1 PRINT DISABLEMENTS 2 PRINT LP TEXT VAL NEXT PAGE EXIT 4 Press 2 to...

Страница 156: ...S PREPARING REPORT PLEASE WAIT CANCEL Press escape at any time to cancel the report 7 While the report is being printed the following screen will be displayed PRINTING LOOP 1 TEXT VALS CANCEL Press es...

Страница 157: ...nti surge sand filled fuse Cable requirements Minimum of 1mm2 copper controlled by a 5A fuse APPENDIX B Gloabal Network Repeater Mechanical And Environmental Specification Mechanical Specification Siz...

Страница 158: ...vides the following outputs 24V supply to motherboard 27 5V float battery charger User fault indications for supply on mains failed and no charge conditions Signals to the motherboard for a common fau...

Страница 159: ...nterface This optional plug in board provides communication with other Premier AL panels and other Global Network Repeaters The board plugs into the repeater interface sockets and provides both repeat...

Страница 160: ...an event on a panel does not cause an action on any other panel c f network cause effect MCP Manual Call Point also know as BGU Network cause effect Cause effect where an event on one panel causes an...

Страница 161: ...tion D FLT Data Fault the analogue value reported by the device is not valid DADDR Double Address two or more devices exist with the same address FUSE FAILED Auxiliary power supply fuse failed LINE FA...

Страница 162: ...120VA Protection T3 15A anti surge sand filled fuse Cable requirements Minimum of 1mm2 copper controlled by a 5A fuse Power Supply Output Specification 24V output 24V 0 5V 3A mains on 21 26V 3A mains...

Отзывы: