3. Press enter to continue. The following screen will be displayed
:
EN/DIS:1=POINTS
2=ZONES, 3=PRINTER
4=SOUNDERS 5=INPUT
SELECT 1..5, <=EXIT
4. Press 5. The following screen will be displayed:
INPUT DISABLEMENT
1=SINGLE, 2=RANGE
3=VIEW
SELECT 1..3, <=EXIT
5. To disable a range of inputs press 2. The following screen will be displayed:
RANGE INPUTS EN/DIS
PANEL? 001
>=ENTER, <=BACK/EXIT
6. Enter the panel number and press enter to continue
.
PAN001 INPUTS EN/DIS
INPUT? 001
>=ENTER, <=BACK/EXIT
7. Enter the first input number and press enter to continue
.
PAN001 INPUTS EN/DIS
INPUTS 001 TO ? 001
>=ENTER, <=BACK/EXIT
8. Enter the number of the second zone and press enter.
PAN001 INPUTS EN/DIS
INPUTS 001 TO 002
1=ENABLE, 2=DISABLE
SELECT 1..2, <=EXIT
9. Choose the option required:
I) To enable the range of inputs displayed press 1
ii) To disable the range of inputs press 2
iii) To exit without making any changes press escape
If the local panel number was entered then the appropriate local inputs will be
enabled/disabled.
If another panel number was entered then a suitable command will be sent via the
network to the appropriate panel.
Page 71 of 111
02/10/03