On network systems these functions only affect the local panel directly, although
changes to zone or control group allocation may indirectly affect other panels that use
those zones or control groups in their own cause/effect.
16.1Engineer Definable Access Code
The engineer’s access code can be changed using the PC cause/effect editor.
Note: If the new code is mislaid then it will not be possible to access the engineer’s
functions. If this occurs, contact your panel supplier. A chargeable site visit will be
required.
16.2Delay Of Operation Of Outputs
This is described in section 15.2.
The engineer can set the delay start and end times, set the delay duration and enable or
disable the delay.
16.3Day/Night Sensitivity Mode
The times of day are only programmable via the P.C. cause/effect editor, and consist
of a start time and an end time for each day of the week. The sensitivity level for each
mode can be set via the menu or the PC cause/effect tool.
16.4Enabling Site Specific Data Changes
All site-specific data is held in non-volatile memory. To protect this from errors the
memory is protected by a write enable switch on the motherboard. This switch has to
be set to the write enable position to allow any changes. If the switch is inadvertently
left in the enable position when the changes are complete the panel indicates a fault
condition.
16.5Point Configuration
The panel loop devices can be automatically reconfigured through an engineer’s menu
command. The panel stores each device address and type on configuration. Any
changes to the loop devices are then indicated as a fault. The system configuration can
also be printed out. This shows all devices on a loop with their status.
The sensitivity of each point can also be changed to allow for ambient conditions.
Fyreye detectors can have the trip level for fire and alert configured.
It is possible using the PC Editor to define addresses on any loop for Platform
Sounders. Any addresses thus configured will have their output command bit 0
operated for the standard sounder controls (evacuate, test alarms, class-change and
one-person alarm walk test).
Note: For compliance with EN54 the fire sensitivity level must be set to 55. The pre-
alarm value can be set to any value
Note: Do not adjust the fire sensitivity level of the Fyreye high temperature heat
detector. This device has an analogue count of 55 at 90 C.
Note: The default levels are:
Fyreye sensor
Default Alert level
45
Default Fire level
55
Valid Alert Levels
35, 40, 45, 50
Valid fire levels
55, 60, 65, 70
Page 31 of 111
02/10/03