Written by: A.C. Amended by GG
Checked by: JBJ
Document Number: USDISC Rev.: 3
Page 40 of 47
19/07/2004
4. Select option 1. The following screen will be displayed:
POINT TEST ZONES
ZONE? 001
>=ENTER, <=BACK/EXIT
5. Enter the zone to be tested and press enter. The following screen will be
displayed:
POINT TEST ZONES
1,
1=ZONE,2=TEST,<=EXIT
6. If another zone is to be included in the test press 1 and add further zones as
necessary. Press 2 to select the test mode.
POINT TEST OPTIONS
1=SILENT
2=WITH SOUNDERS
SELECT 1..2, <=EXIT
7. Select the required test mode by pressing ‘1’ or ‘2’ as appropriate. The screen
will indicate test mode is active.
POINT TEST ACTIVE
1,
1=CANCEL TEST,<=EXIT
In addition the TEST LED will be illuminated
When the test is complete press 1 to cancel the test mode.
How To Test Sounding Devices Using One Person Test Mode
In this test all of the alarms will sound for 5 seconds every 10 seconds for audibility
checking. This applies to the local alarm circuits, all alarm controller ancillary devices
and loop powered sounders. This test mode will be automatically cancelled if a fire
condition occurs.
1. Enter the user menu as described in section 6.
2. Press 5 to select option 5 - Test. The following screen will be displayed:
TEST MODE
1=VIEW POINT STATUS
2=ONE PERSON TESTS
SELECT 1..2, <=EXIT
3. Press 2 to enter the one person test mode. The following screen will be
displayed:
ONE PERSON TEST
1=POINT WALK TEST
2=ALARM WALK TEST
SELECT 1..2, <=EXIT
4. Select option 2 to begin the alarm test. The following screen will be displayed: