When one of this modes is configured, the access to its configuration window
appears in the lateral menu:
9
Heating
It can be configured:
Freezing protection
and the corresponding temperature.
Control
method
for thermostat:
2-Point control
or
PI Control
.
The
2-Point control
requires configuring both the lower and
upper hysteresis.
The
PI Control
may be applied following two different Control
Types:
Continuous
or
PWM
. It requires the introduction of the
cycle time and the control parameters:
x
Warm Water [5k-150min]
x
Floor Heating [5k-240min]
x
Electric Heating [4k-100min]
x
Blow Convector [4k-90min]
x
A/A Split [4k-90min]
x
Customized
: this option requires the introduction of
the proportional band (ºK) and the integral time for
the PI calculus.
Additional Heating
and additional heating band.
Figure 17 Heating mode configuration
9
Cooling
It can be configured:
Overheating Protection
and the corresponding temperature.
Control
method
for thermostat:
2-Point
control or
PI Control
.