ZENN
iO
AVANCE
Y
TECNOLOGÍA
www.zennio.com
3
1
¾
Sending of “0”Delay
: value between 0 and 255, in seconds.
¾
Sending of “1” Delay
: value between 0 and 255, in seconds.
¾
Periodical sending of “0”:
value between 0 and 255, in seconds. The
value “0” indicates that the periodical sending is not activated.
¾
Periodical sending of “1”:
value between 0 and 255, in seconds. The
value “0” indicates that the periodical sending is not activated.
Other available functionalities for the inputs are:
¾
Block:
Yes or No. It enables a 1-bit communication object that allows
blocking the input (value “1”
→
blocked input).
¾
Sending status (“0” y “1”) on bus voltage recovery
: this option
allows configuring an automatic sending of the input status after a
voltage recovery, with a sending delay (value between 2 and 255, in
seconds).
Figure 23 Switching/Sensor Configuration
Temperature probe
When configuring an input as a temperature probe, the following options can be
configured:
¾
Temperature sensor calibration:
value between -50 and 50, in tenths
of a degree.