ZENN
iO
AVANCE
Y
TECNOLOGÍA
www.zennio.com
3
2
¾
Temperature sending period:
value between 0 and 100, in tenths of a
degree. The value “0” indicates that this option is disabled.
¾
Send with a temperature change
: value between 0 and 200, in tenths
of a degree. The value “0” indicates that this option is disabled.
On the other hand, two communication objects of 1-bit length can be enabled
for temperature protection (overheating or overcooling):
¾
Temperature protection:
No, Overheating, Overcooling
or
Overheating
and overcooling.
According to the selected option, it will be necessary introducing the
temperature for overheating and overcooling or both (value between -30 and
50, in degrees), and the hysteresis for a correct operation, in tenths of degree
(value between 1 and 50).
Figure 24 Temperature Sensor Configuration
6.5. BUTTONS
The window
Buttons
allows configuring the
8 direct access buttons
for working in
couple or individually:
Buttons 1-2:
Disabled, Individual or Couple.
Buttons 3-4:
Disabled, Individual or Couple.
Buttons 5-6:
Disabled, Individual or Couple.
Buttons 7-8:
Disabled, Individual or Couple.
Arrow buttons. Yes or No.