MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
51
ANNEX II: COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the
specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - - W -
DPT_Switch
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - - W -
DPT_Switch
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
5, 35
2
Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 1
External Sensor Temperature
6, 36
2
Bytes
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 2
External Sensor Temperature
7, 37
2
Bytes
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Effective Temperature
Effective Control Temperature
8, 38
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Protection
[Tx] Special Mode
1-byte HVAC Mode
9, 39
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: comfort
0 = Off; 1 = On
10, 40
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: standby
0 = Off; 1 = On
11, 41
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: economy
0 = Off; 1 = On
12, 42
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: protection
0 = Off; 1 = On
13, 43
1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (input)
0 = Closed; 1 = Open
14, 44
1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
15, 45
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
[Tx] Special Mode Status
1-byte HVAC Mode