MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
58
360
1 Bit
I
C - - W -
DPT_Switch
0/1
[FCVx] Manual Fan: Speed 4
0 = Off; 1 = On
361
1 Bit
O
C T R - -
DPT_State
0/1
[FCVx] Fan: Speed 0 (Status)
0 = Inactive; 1 = Active
362
1 Bit
O
C T R - -
DPT_State
0/1
[FCVx] Fan: Speed 1 (Status)
0 = Inactive; 1 = Active
363
1 Bit
O
C T R - -
DPT_State
0/1
[FCVx] Fan: Speed 2 (Status)
0 = Inactive; 1 = Active
364
1 Bit
O
C T R - -
DPT_State
0/1
[FCVx] Fan: Speed 3 (Status)
0 = Inactive; 1 = Active
365
1 Bit
O
C T R - -
DPT_State
0/1
[FCVx] Fan: Speed 4 (Status)
0 = Inactive; 1 = Active
366
1 Bit
I
C - - W -
DPT_Ack
0/1
[FCVx] Unfreeze Alarm
Alarm=in Unfreeze=1 => End Alarm
367
1 Bit
I
C - - W -
DPT_Alarm
0/1
[FCVx] Alarm 1: Trigger
0 = Active; 1 = Inactive
1 Bit
I
C - - W -
DPT_Alarm
0/1
[FCVx] Alarm 1: Trigger
0 = Inactive; 1 = Active
368
1 Bit
I
C - - W -
DPT_Alarm
0/1
[FCVx] Alarm 2: Trigger
0 = Active; 1 = Inactive
1 Bit
I
C - - W -
DPT_Alarm
0/1
[FCVx] Alarm 2: Trigger
0 = Inactive; 1 = Active
369
1 Byte
I
C - - W -
DPT_Value_1_Ucount
0 - 255
[FCVx] Manual Fan: Enumeration Control
0 = S0; 1 = S1
1 Byte
I
C - - W -
DPT_Value_1_Ucount
0 - 255
[FCVx] Manual Fan: Enumeration Control
0 = S0; 1 = S1; 2 = S2
1 Byte
I
C - - W -
DPT_Value_1_Ucount
0 - 255
[FCVx] Manual Fan: Enumeration Control
0 = S0; 1 = S1; 2 = S2; 3 = S3
1 Byte
I
C - - W -
DPT_Value_1_Ucount
0 - 255
[FCVx] Manual Fan: Enumeration Control
0 = S0; 1 = S1; 2 = S2; 3 = S3; 4 = S4
370
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCVx] Fan: Speed Enumeration (Status)
0 = S0; 1 = S1
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCVx] Fan: Speed Enumeration (Status)
0 = S0; 1 = S1; 2 = S2
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCVx] Fan: Speed Enumeration (Status)
0 = S0; 1 = S1; 2 = S2; 3 = S3
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[FCVx] Fan: Speed Enumeration (Status)
0 = S0; 1 = S1; 2 = S2; 3 = S3; 4 = S4
371
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Manual Fan: Percentage Control
[0]% = S0; [0.4...100]% = S1
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Manual Fan: Percentage Control
[0]% = S0; [0.4...50.2]% = S1; [50.6...100]% = S2
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Manual Fan: Percentage Control
[0]% = S0; [0.4...33.3]% = S1; [33.7...66.7]% = S2;
[67.1...100]% = S3
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Manual Fan: Percentage Control
[0]% = S0; [0.4...25.1]% = S1; [25.5...50.2]% = S2;
[50.6...75.3]% = S3; [75.5...100]%= S4
372
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCVx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCVx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 50.2%; S2 = 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCVx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 33.3%; S2 = 66.7%; S3 = 100%
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCVx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 25.1%; S2 = 50.2%; S3 = 75.3%; S4 =
100%
373
2
Bytes
I/O
C T R W -
DPT_TimePeriodSec
0-3600
[FCVx] Manual Fan: Duration of Manual
Override
1 - 3600 S (0 = Disable)
2
Bytes
I/O
C T R W -
DPT_TimePeriodMin
0-1440
[FCVx] Manual Fan: Duration of Manual
Override
1 - 1440 Min (0 = Disable)
2
Bytes
I/O
C T R W -
DPT_TimePeriodHrs
0-24
[FCVx] Manual Fan: Duration of Manual
Override
1 - 24 H (0 = Disable)
374
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Cooling Input Control Signal
[0…100]%
375
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[FCVx] Heating Input Control Signal
[0…100]%