ETS PARAMETERISATION
After enabling “
Alarms
” in the Configuration screen (see section 2.5.1), a new tab will
be incorporated into the tab tree on the left.
Figure 7
Fan Coil – Alarms.
While the parameters of alarm no. 1 are shown by default, those of alarm 2 require
marking the corresponding checkbox.
Deactivation – Mode
: “Normal” (default) or “Frozen (Acknowledgement
Needed)”. The second option enables a new 1-bit object, “
[FCV1] Unfreeze
Alarm
”, which should be used for externally unfreezing the alarm once
“
[FCV1] Alarm
” has received the no-alarm value (i.e., the inverse of the
trigger value).
Note
:
the acknowledgement should be sent necessarily after “[FCV1] Alarm”
has acquired the no-alarm value. Sending it while the trigger value is still
active will have no effect
.
Trigger
: sets the value (“1” –default– or “0”) that, when received from the
KNX bus through object “
[FCV1] Alarm
” (or “
[FCV1] Alarm 2
” for alarm
number 2), will be interpreted by the device as an alarm trigger and will
therefore initiate the action configured below.