MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
25
“
[FCV1] Valve: Purge Heating Valve
”,
“
[FCV1] Valve: Purge Cooling Valve
”.
If only one valve is available, they will be replaced by a sole object: “
[FCV1] Valve:
Purge
”.
Writing the value “1” to any of these objects triggers the purge of the corresponding
valve, while value “0” interrupts it.
The following parameters are shown:
Purge Duration
: time lapse the valve will remain in the purge state once the
function has been triggered (from 10 to 3600 seconds, where 10 seconds is
the default value).
Valve Position
: valve opening level during the purge process (value from 0
to 100%, where 100% is the default value).