MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
16
FAN CONTROL CONFIGURATION
Number of Fan Speeds
: up to four fan speeds can be controlled, depending
on the fan model. This determines the number of relays required (unneeded
relay outputs may be configured as individual binary outputs; see section
2.3).
Type of Relays Control
(only available if the above is set to other than “1”):
“Switching” (default setting): the activation of each speed requires
closing one specific relay (and leaving the others open).
It is possible to set up a
Delay between Fan Speed Switching
(between 3 and 100 ds), which represents the time between the opening
of the source speed relay and the closing of the target speed relay (so
both stay open during such time).
“Accumulation”: the speed will be proportional to the number of active
outputs (i.e. closed relays), which therefore get triggered in sequence.
ADVANCED GENERAL CONFIGURATION
Fan Coil always On
:
If this option is set to “No” (by default), the fan coil turns on/off when
receiving a “1” or “0” through the object “
[FCV1] On/Off
”. The state of
the fan coil can be obtained by reading the “
[FCV1] On/Off (Status)
”
communication object any time.
If this option is set to “Yes”, the Fan Coil remains always on, waiting for
regulation orders. The objects “
[FCV1] On/Off
” and “
[FCV1] On/Off
(Status)
” are not available.
Automatic Air Recirculation in Cooling Mode
: sets whether the fan should
always remain on while in the Cooling mode or not.
Ventilation Mode
: sets whether the ventilation mode is enabled or not. If
enabled, the communication objects “
[FCV1] Ventilation Mode
” (which
triggers / stops the ventilation mode when it receives the values “1” and “0”,
respectively) and “
[FCV1] Ventilation Mode (Status)
” will be incorporated to