MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
43
2.5.3.3
CUSTOM START
In certain systems, it may be a requirement that, whenever the fan is turned on after
being idle,
it remains at a certain speed for some instants
, to ensure enough torque
prior to normal operation (i.e., prior to switching to the fan speed determined by the fan
coil module or by the user).
MAXinBOX FC 0-10V VALVE provides the custom start function to meet such
requirement.
ETS PARAMETERISATION
The Custom Start screen is accessible after enabling such function (see section 2.5.3).
It contains the following parameters:
Figure 19.
Fan Coil – Custom Start
Custom Start Speed
: sets the speed the fan must remain at, during the start-
up.
Custom Start Duration
: sets the time (from 0 to 3600 seconds) the fan must
remain at the above speed, prior to resuming normal operation.