MAXinBOX FC 0-10V VALVE
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
49
ETS PARAMETERISATION
The manual control
is configured from a specific tab which can be enabled from the
General screen (see section 2.1).
Figure 20
Manual Control.
The only two parameters are:
Manual Control
: options are “Disabled”, “Only Test Mode Off”, “Only Test
Mode On” and “Test Off Mode + Test On Mode” (default). Depending on the
selection, the device will permit using the manual control under the Test Off,
the Test On, or either of the two modes. Note that, as stated before, using the
Test Off mode does not require any special action, while switching to the Test
On mode does require long-pressing the Prog./Test button.
Lock Manual Control
: unless the above parameter has been “Disabled”,
enabling the Lock Manual Control parameter will provide a runtime procedure
for locking the manual control. When this checkbox is enabled, object
“
Manual Control Lock
” turns visible, as well as two more parameters:
Value
: defines whether the lock/unlock of the manual control should take
place respectively upon the reception (through the aforementioned object)
of values “0” and “1”, or the opposite.
Initialization
: sets how the manual control should remain after the device
start-up (after an ETS download or a bus power failure): “Unlocked”,
“Locked” or, by default, “Last Value” (on the very first start-up, this will be
Unlocked).