2.5.1.3
PURGE
The configuration of the valve allows
enabling a purge function
(one per valve),
which consists in opening the selected valve and stopping the fan for a configurable
time space.
The purge
begins
when one “1” is received through the corresponding object, and ends
when the parameterised time elapses, when one “0” arrives, when a bus failure takes
place, when the fan coil control module is turned off, or when the user enters the Test
On mode (see section 2.8). To restart the process (from the beginning), the
corresponding object should be written again with a “1”.
Notes
:
Any control order or any mode switch request received during the purge
function
will be executed after the purge ends
.
Any
alarm or switch-off
order will stop the purge process and will be executed.
During the alarm or switch-off state, purge orders will be ignored.
If no control orders are received, once the
purge
is over the fan coil control
module
will recover the previous state
.
ETS PARAMETERISATION
After enabling
Purge
in the Configuration screen (see section 2.5.1), a new tab will be
incorporated into the tree on the left.
Figure 9
. Fan coil - Purge.
Two new communication objects are also incorporated (together with their
corresponding status objects).