ALLinBOX 1612 v2
Technical Support:
38
(1 bit)
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Cooling Valve: Control Variable
(1 bit)
0 = Close Valve; 1 = Open Valve
437, 470
1 Bit
I
C - W - U
DPT_OpenClose
0/1
[FCx] Heating Valve: Control Variable
(1 bit)
0 = Open Valve; 1 = Close Valve
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Heating Valve: Control Variable
(1 bit)
0 = Close Valve; 1 = Open Valve
438, 471
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Cooling Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Cooling Valve (Status)
0 = Closed; 1 = Open
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Valve (Status)
0 = Closed; 1 = Open
439, 472
1 Bit
O
C R - T -
DPT_OpenClose
0/1
[FCx] Heating Valve (Status)
0 = Open; 1 = Closed
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Heating Valve (Status)
0 = Closed; 1 = Open
440, 473
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Cooling Valve: Anti-Seize
Protection (Status)
0 = Not Active; 1 = Active
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Valve: Anti-Seize Protection
(Status)
0 = Not Active; 1 = Active
441, 474
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Heating Valve: Anti-Seize
Protection (Status)
0 = Not Active; 1 = Active
442, 475
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Valve (Status)
0 - 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Cooling Valve (Status)
0 - 100%
443, 476
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Heating Valve (Status)
0 - 100%
444, 477
1 Bit
O
C R - T -
DPT_Bool
0/1
[FCx] Control Value - Error
0 = No Error; 1 = Error
445, 478
2
Bytes
I
C - W - U
DPT_Value_Temp
-273.00º - 670433.28º
[FCx] Ambient Temperature
Ambient Temperature
446, 479
2
Bytes
I
C - W - U
DPT_Value_Temp
-273.00º - 670433.28º
[FCx] Setpoint Temperature
Setpoint Temperature
447, 480
2
Bytes
I/O
C R W T U
DPT_TimePeriodMin
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 1440 min
2
Bytes
I/O
C R W T U
DPT_TimePeriodHrs
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 24 h
513, 519, 525, 531, 537,
543, 549, 555, 561, 567,
573, 579
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] Input Lock
0 = Unlock; 1 = Lock
514, 520, 526, 532, 538,
544, 550, 556, 562, 568,
574, 580
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 0
Sending of 0
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 1
Sending of 1
1 Bit
I
C - W T -
DPT_Switch
0/1
[Ix] [Short Press] 0/1 Switching
Switching 0/1
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up Shutter
Sending of 0 (Up)
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Down Shutter
Sending of 1 (Down)