1.5
HARD RESET TO FACTORY DEFAULTS
By
pressing the "IP Factory Reset" button for three seconds
:
The device will adopt an
IP address via the DCHP server
.
➢
If the DHCP client does not obtain a valid IP address (after several
attempts), then the device will be assigned an
IP address via the AutoIP
(APIPA)
1
protocol.
The factory reset indicator LED will light up in red.
If a
second-long press
is made on the "IP Factory Reset" button
The device will adopt a
static IP address
.
➢
If "Use a static IP address" has been chosen in the ETS configuration, the
device will have the
configured IP
.
The factory reset led will light up in green.
➢
If, on the other hand, in the ETS configuration "Obtain an IP address
automatically" has been chosen, the device will obtain an
IP by means of
AutoIP (APIPA)
.
The factory reset indicator LED lights up yellow.
The factory IP setting and the colour of the factory reset LED will remain until the
device is restarted.
The following table summarizes the above:
Press
ETS Configuration
IP Configuration
LED
1
st
long press
(3s)
Obtain an IP automatically
IP obtained by DHCP.
(If a valid IP is not obtained
IP by APIPA)
Red
Use a static IP address
2
nd
long
press (3s)
Obtain an IP automatically
IP obtained by APIPA
Yellow
Use a static IP address
Static IP of ETS configuration
Green
1