ALLinBOX 1612 v2
Technical Support:
48
1233, 1301, 1369, 1437
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[HTx] [D] Window Status 4 (Input)
0 = Closed; 1 = Open
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[HTx] [D] Window Status 4 (Input)
0 = Open; 1 = Closed
1234, 1302, 1370, 1438
1 Bit
I/O
C R W - -
DPT_Enable
0/1
[HTx] [D] Enable Window Status
0 = Disabled; 1 = Enabled
1235, 1303, 1371, 1439
1 Bit
I/O
C R W - -
DPT_Enable
0/1
[HTx] [D] Thermostat Lock
0 = Locked; 1 = Unlocked
1 Bit
I/O
C R W - -
DPT_Enable
0/1
[HTx] [D] Thermostat Lock
0 = Unlocked; 1 = Locked
1236, 1304, 1372, 1440
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [D] Comfort Lower Limit
[-20°C, 100°C]
1237, 1305, 1373, 1441
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [D] Comfort Upper Limit
[-20°C, 100°C]
1238, 1306, 1374, 1442
1 Bit
I/O
C R W - -
DPT_Switch
0/1
[HTx] [D] Hidden Offset On/Off
0 = Off; 1 = On
1239, 1307, 1375, 1443
2
Bytes
I/O
C R W T U
DPT_Value_Tempd
-671088.64º - 670433.28º
[HTx] [D] Hidden Offset Value
[-20°C, 100°C]
1240, 1308, 1376, 1444
1 Bit
O
C R - T -
DPT_Bool
0/1
[HTx] [D] Eco Mode Notification
0 = Out of eco range; 1 = Setpoint
in Eco Range
1241, 1309, 1377, 1445
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[HTx] [D] Eco Mode Ratio
Percentage of Time Working in Eco
Range
1242, 1310, 1378, 1446
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [D] Eco Mode: Lower Limit
(Cooling)
Lower Value for the Ecological
Range
1243, 1311, 1379, 1447
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [D] Eco Mode: Upper Limit
(Heating)
Upper Value for the Ecological
Range
1244, 1312, 1380, 1448
2
Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [D] Setpoint to Split
[-20°C, 100°C]
1245, 1313, 1381, 1449
2
Bytes
I
C - W - -
DPT_Value_Humidity
-12% - 12%
[HTx] [F] Current Humidity
Humidity Sensor Value
1246, 1314, 1382, 1450
2
Bytes
I/O
C R W T U
DPT_Value_Humidity
-12% - 12%
[HTx] [F] High Humidity Alarm
Threshold
Value of High Humidity Alarm
Threshold
1247, 1315, 1383, 1451
1 Bit
I/O
C R W T U
DPT_Enable
0/1
[HTx] [F] Dehumidification Control
0 = Disabled; 1 = Enabled
1248, 1316, 1384, 1452
1 Bit
O
C R - T -
DPT_Bool
0/1
[HTx] [F] Dehumidification Status
0 = No Dehumidifying; 1 =
Dehumidifying
1249, 1317, 1385, 1453
1 Bit
O
C R - T -
DPT_Alarm
0/1
[HTx] [F] High Humidity
0 = No Alarm; 1 = Alarm
1250, 1318, 1386, 1454
1 Bit
I/O
C R W T U
DPT_Enable
0/1
[HTx] [F] Enable Apparent
Temperature
0 = Room Temperature; 1 =
Apparent Temperature
1251, 1319, 1387, 1455
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[HTx] [Cooling] Control Variable
PI Control (Continuous)
1252, 1320, 1388, 1456
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[HTx] [Heating] Control Variable
PI Control (Continuous)
1253, 1321, 1389, 1457
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [Cooling] Control Variable
2-Point Control
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [Cooling] Control Variable
PI Control (PWM)
1254, 1322, 1390, 1458
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [Heating] Control Variable
2-Point Control
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [Heating] Control Variable
PI Control (PWM)
1255, 1323, 1391, 1459
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [Cooling] Additional Cool
Temp >= (SBand) => "1"