ALLinBOX 1612 v2
Technical Support:
42
881, 910
3=Economy
4=Building
Protection
592, 621, 650, 679, 708,
737, 766, 795, 824, 853,
882, 911
1 Bit
O
C R - T -
DPT_Switch
0/1
[Ix] Presence State (Binary)
Binary Value
1 Bit
O
C R - T -
DPT_Start
0/1
[Ix] Presence: Slave Output
1 = Motion Detected
593, 622, 651, 680, 709,
738, 767, 796, 825, 854,
883, 912
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[Ix] Presence Trigger
Binary Value to Trigger the Presence
Detection
594, 623, 652, 681, 710,
739, 768, 797, 826, 855,
884, 913
1 Bit
I
C - W - -
DPT_Start
0/1
[Ix] Presence: Slave Input
0 = Nothing; 1 = Detection from
slave device
595, 624, 653, 682, 711,
740, 769, 798, 827, 856,
885, 914
2
Bytes
I
C - W - -
DPT_TimePeriodSec
0 - 65535
[Ix] Presence: Waiting Time
0-65535 s.
596, 625, 654, 683, 712,
741, 770, 799, 828, 857,
886, 915
2
Bytes
I
C - W - -
DPT_TimePeriodSec
0 - 65535
[Ix] Presence: Listening Time
1-65535 s.
597, 626, 655, 684, 713,
742, 771, 800, 829, 858,
887, 916
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] Presence: Enable
According to parameters
598, 627, 656, 685, 714,
743, 772, 801, 830, 859,
888, 917
1 Bit
I
C - W - -
DPT_DayNight
0/1
[Ix] Presence: Day/Night
According to parameters
599, 628, 657, 686, 715,
744, 773, 802, 831, 860,
889, 918
1 Bit
O
C R - T -
DPT_Occupancy
0/1
[Ix] Presence: Occupancy State
0 = Not Occupied; 1 = Occupied
600, 629, 658, 687, 716,
745, 774, 803, 832, 861,
890, 919
1 Bit
I
C - W - -
DPT_Start
0/1
[Ix] External Motion Detection
0 = Nothing; 1 = Motion detected
by an external sensor
601, 606, 611, 630, 635,
640, 659, 664, 669, 688,
693, 698, 717, 722, 727,
746, 751, 756, 775, 780,
785, 804, 809, 814, 833,
838, 843, 862, 867, 872,
891, 896, 901, 920, 925,
930
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[Ix] [Cx] Detection State (Scaling)
0-100%
602, 607, 612, 631, 636,
641, 660, 665, 670, 689,
694, 699, 718, 723, 728,
747, 752, 757, 776, 781,
786, 805, 810, 815, 834,
1 Byte
O
C R - T -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Ix] [Cx] Detection State (HVAC)
Auto, Comfort, Standby, Economy,