ALLinBOX 1612 v2
Technical Support:
37
1 Bit
O
C R - T -
DPT_Enable
0/1
[FCx] Fan: Manual/Automatic (Status)
0 = Manual; 1 = Automatic
421, 454
1 Bit
I
C - W - U
DPT_Step
0/1
[FCx] Manual Fan: Step Control
0 = Down; 1 = Up
422, 455
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 0
0 = Off; 1 = On
423, 456
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 1
0 = Off; 1 = On
424, 457
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 2
0 = Off; 1 = On
425, 458
1 Bit
I
C - W - U
DPT_Switch
0/1
[FCx] Manual Fan: Speed 3
0 = Off; 1 = On
426, 459
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Fan: Speed 0 (Status)
0 = Off; 1 = On
427, 460
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Fan: Speed 1 (Status)
0 = Off; 1 = On
428, 461
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Fan: Speed 2 (Status)
0 = Off; 1 = On
429, 462
1 Bit
O
C R - T -
DPT_Switch
0/1
[FCx] Fan: Speed 3 (Status)
0 = Off; 1 = On
430, 463
1 Byte
I
C - W - U
DPT_Fan_Stage
0 - 255
[FCx] Manual Fan: Enumeration
Control
S0 = 0; S1 = 1; S2 = 2; S3 = 3
1 Byte
I
C - W - U
DPT_Fan_Stage
0 - 255
[FCx] Manual Fan: Enumeration
Control
S0 = 0; S1 = 1; S2 = 2
1 Byte
I
C - W - U
DPT_Fan_Stage
0 - 255
[FCx] Manual Fan: Enumeration
Control
S0 = 0; S1 = 1
431, 464
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1; S2 = 2; S3 = 3
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1; S2 = 2
1 Byte
O
C R - T -
DPT_Fan_Stage
0 - 255
[FCx] Fan: Speed Enumeration
(Status)
S0 = 0; S1 = 1
432, 465
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
S0 = 0%; S1 = 0,4-33,3%; S2 =
33,7-66,7%; S3 = 67,1-100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
S0 = 0%; S1 = 1-50%; S2 = 51-
100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Manual Fan: Percentage Control
S0 = 0%; S1 = 1-100%
433, 466
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 33,3%; S2 =
66,6%; S3 = 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 1-50%; S2 = 51-
100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[FCx] Fan: Speed Percentage (Status)
S0 = 0%; S1 = 1-100%
434, 467
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Cooling Fan: Continuous Control
0 - 100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Cooling Valve: PI Control
(Continuous)
0 - 100%
435, 468
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Heating Fan: Continuous Control
0 - 100%
1 Byte
I
C - W - U
DPT_Scaling
0% - 100%
[FCx] Heating Valve: PI Control
(Continuous)
0 - 100%
436, 469
1 Bit
I
C - W - U
DPT_OpenClose
0/1
[FCx] Cooling Valve: Control Variable 0 = Open Valve; 1 = Close Valve