ALLinBOX 1612 v2
Technical Support:
46
1 Bit
I
C - W T U
DPT_Switch
0/1
[HTx] [A] Fan: Manual/Automatic
0 = Automatic; 1 = Manual
1203, 1271, 1339, 1407
1 Bit
O
C R - T -
DPT_Switch
0/1
[HTx] [A] On/Off Fancoil
0 = Off; 1 = On
1204, 1272, 1340, 1408
1 Bit
I
C - W - -
DPT_Reset
0/1
[HTx] [B] User Comfort Setpoint Reset
0 = Nothing; 1 = Reset
1205, 1273, 1341, 1409
2
Bytes
I
C - W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] User Setpoint Control
[-20°C, 100°C]
2
Bytes
I
C - W T U
DPT_Value_Tempd
-671088.64º - 670433.28º
[HTx] [B] User Setpoint Offset
[-15°C, 15°C]
1206, 1274, 1342, 1410
1 Bit
I
C - W - -
DPT_Step
0/1
[HTx] [B] Step User Setpoint
0 = Decrease; 1 = Increase
1207, 1275, 1343, 1411
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Comfort Setpoint (Cooling)
[-20°C, 100°C]
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Comfort Setpoint
[-20°C, 100°C]
1208, 1276, 1344, 1412
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Standby Setpoint (Cooling)
[-20°C, 100°C]
1209, 1277, 1345, 1413
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Economy Setpoint (Cooling)
[-20°C, 100°C]
1210, 1278, 1346, 1414
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Protection Setpoint
(Cooling)
[-20°C, 100°C]
1211, 1279, 1347, 1415
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Comfort Setpoint (Heating)
[-20°C, 100°C]
1212, 1280, 1348, 1416
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Standby Setpoint (Heating)
[-20°C, 100°C]
1213, 1281, 1349, 1417
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Economy Setpoint (Heating)
[-20°C, 100°C]
1214, 1282, 1350, 1418
2
Bytes
I/O
C R W T U
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Protection Setpoint
(Heating)
[-20°C, 100°C]
1215, 1283, 1351, 1419
2
Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] Real Setpoint Status
[-20°C, 100°C]
1216, 1284, 1352, 1420
2
Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[HTx] [B] User Setpoint Status
[-20°C, 100°C]
2
Bytes
O
C R - T -
DPT_Value_Tempd
-671088.64º - 670433.28º
[HTx] [B] User Setpoint Offset Status
[-15°C, 15°C]
1217, 1285, 1353, 1421
2
Bytes
I/O
C R W T U
DPT_TimePeriodSec
0 - 65535
[HTx] [C] Transition Time: Comfort to
Default Mode
Seconds (0 = Disabled)
2
Bytes
I/O
C R W T U
DPT_TimePeriodMin
0 - 65535
[HTx] [C] Transition Time: Comfort to
Default Mode
Minutes (0 = Disabled)
2
Bytes
I/O
C R W T U
DPT_TimePeriodHrs
0 - 65535
[HTx] [C] Transition Time: Comfort to
Default Mode
Hours (0 = Disabled)
1218, 1286, 1354, 1422
2
Bytes
I/O
C R W T U
DPT_TimePeriodSec
0 - 65535
[HTx] [C] Transition Time: Standby to
Economy
Seconds (0 = Disabled)