ALLinBOX 1612 v2
Technical Support:
26
➢
Binary Value
[
disabled/
enabled
]
: if checked, object “
[ML] General
Switch-off: Binary Object
” will be enabled, which will send one “0”
whenever the general switch-off takes off.
➢
Scaling
[
disabled
/enabled
]
: if checked, object “
[ML] General Switch-off:
Scaling
” will be enabled, which will send a percentage value (configurable
in
Value
[
0
…100
]) whenever the general switch-off takes off.
➢
Scene
[
disabled
/enabled
]
: if checked, object “
[ML] General Switch-off:
Scene
” will be enabled, which will send a scene run / save order
(configurable in
Action
[
Run
/ Save
] and
Scene Number
[
1
…64
])
whenever the general switch-off takes off
➢
HVAC
[
disabled
/enabled
]
: if checked, object “
[ML] General Switch-off:
HVAC mode
” will be enabled, which will send an HVAC thermostat mode
value (configurable in
Value
[
Auto / Comfort / Standby /
Economy
/
Building Protection
) whenever the general switch-off takes off
Note
:
the above options are not mutually exclusive; it is possible to send
values of different nature together
.
Courtesy Switch-On
:
The parameters available here are entirely analogous to those already
mentioned for General Switch-Off. However, in this case the names of the
objects start with “
[ML] Courtesy Switch-
On (…)
”. On the other hand,
sending
scene save orders
is not possible for the courtesy switch-on (only
orders to play scenes are allowed).
Note
:
object “[ML] Courtesy Switch-On: Binary Object” sends the value “1”
(when the courtesy switch-
on takes place), in contrast to object “[ML]
General Switch-Off: Binary Object
”, which sends the value “0” (during the
general switch-off, as explained above)
.