ALLinBOX 1612 v2
Technical Support:
32
Disabled output
: short and long presses will switch the state of the
corresponding relay. In case this consists in closing the relay, then the
remaining relays of its block will open, for safety reasons.
As described previously if the device is in Test On mode, any command sent from the
KNX bus to the actuator will not affect the outputs and no status objects will be sent
(only periodically timed objects such as Heartbeat or logic functions will continue to be
sent to the bus) while Test ON mode is active. However, in the case of the "Alarm" and
"Block" objects, although in Test ON mode the actions received by each object are not
taken into account, the evaluation of their status is carried out when exiting this mode,
so that any change in the alarm status or blocking of the outputs while Test ON mode
is active is taken into account when exiting this mode and is updated with the last
status detected.
ETS PARAMETERISATION
After enabling “
Manual Control with IR
” in the “General” screen (see section 2.4), a
new tab will be incorporated into the tree on the left.
The only two parameters are:
Figure 16.
Manual Control
Manual Control
[
Disabled /
Test On Mode
]: depending on the selection, the
device will permit using the manual control under the Test On or have it
disabled. Note that, as stated before, using Test On mode does require long-
pressing the Prog/Test button.
Important
:
the device is factory delivered from factory with all the output disabled,
and with manual control Test On mode enabled
.