ALLinBOX 1612 v2
Technical Support:
34
ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5, 16, 27, 38, 49, 60, 71, 82,
93, 104, 115, 126, 137, 148,
159, 170
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Ox] Scenes
0
–
63 (Execute 1
–
64); 128
–
191
(Save 1
–
64)
6, 17, 28, 39, 50, 61, 72, 83,
94, 105, 116, 127, 138, 149,
160, 171
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.O. (0=Open Relay; 1=Close
Relay)
1 Bit
I
C - W - -
DPT_BinaryValue
0/1
[Ox] On/Off
N.C. (0=Close Relay; 1= Open
Relay)
7, 18, 29, 40, 51, 62, 73, 84,
95, 106, 117, 128, 139, 150,
161, 172
1 Bit
O
C R - T -
DPT_BinaryValue
0/1
[Ox] On/Off (Status)
0=Output Off; 1=Output On
8, 19, 30, 41, 52, 63, 74, 85,
96, 107, 118, 129, 140, 151,
162, 173
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ox] Lock
0=Unlock; 1=Lock
9, 20, 31, 42, 53, 64, 75, 86,
97, 108, 119, 130, 141, 152,
163, 174
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Timer
0=Switch Off; 1=Switch On
10, 21, 32, 43, 54, 65, 76,
87, 98, 109, 120, 131, 142,
153, 164, 175
1 Bit
I
C - W - -
DPT_Start
0/1
[Ox] Flashing
0=Stop; 1=Start
11, 22, 33, 44, 55, 66, 77,
88, 99, 110, 121, 132, 143,
154, 165, 176
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Normal; 1=Alarm
1 Bit
I
C - W - -
DPT_Alarm
0/1
[Ox] Alarm
0=Alarm; 1=Normal
12, 23, 34, 45, 56, 67, 78,
89, 100, 111, 122, 133, 144, 1 Bit
I
C - W - -
DPT_Ack
0/1
[Ox] Unfreeze Alarm
Alarm=0 + Unfreeze=1 => End
Alarm