Display indication
Description
Reaction of the system Solution
The controller is
equipped with
an electronic
protection
system against
too low voltages
of the power
supply.
In the event of too
low voltages, the
operation of the system
is stopped. If the
appropriate voltage
value is restored,
then the operation
will automatically be
restarted.
• The power grid has to be
checked.
• The cross-section of the
power supply cable for
the converter is too small.
Replace the cable with one
with a suitable cross-section.
While doing so, take into
consideration the voltage
drop on the controller’s
supply point.
• The power supply cable for
the controller is too long.
Replace the cable with one
with a bigger cross-section.
While doing so, take into
consideration the voltage
drop on the controller’s
supply point.
No indication
• It has to be made sure that a
power supply of
230 V is available. If there
are normal power supply
conditions, then the fuse (20
A) located on the main circuit
board has to be checked.
Chapter 5.5 “Electrical
connection of the controller
ZP SPEEDCONTROL
COMFORT“