background image

YSI 5200A
     95

YSI 5200A
     94

Subnet Mask

Menus → System → Communications → Ethernet → Subnet Mask

A Subnet mask address can only be configured when DHCP is disabled. The subnet 
mask number helps to define the relationship between the host (computers, routers, 
switches, etc.) and the rest of the network.  Consult the network administrator when 
configuring this menu.

Notes:

 

-

When DHCP is enabled, the Subnet Mask address is not updated at the Subnet 
Mask menu.

 

-

AquaManager users should program the Subnet mask either by force serial port 
in the AquaManager Communication menu or locally at the 5200A.  Poll node 
using RS232 communication to upload configuration information including:  
static IP, port, subnet, and gateway addresses.

 

-

Numbers between 0-255 are valid for each of the four (4) Subnet Mask IP 
Address fields.

Gateway

Menus → System → Communications → Ethernet → Gateway

The Gateway address can only be configured when DHCP is disabled.  A gateway IP 
refers to a device on a network which sends local network traffic to other networks.  
Consult the network administrator when configuring this menu.
Notes:

 

-

When DHCP is enabled, the Gateway address is not updated at the Gateway 
menu.

 

-

AquaManager users should program the Gateway address either by force se-
rial port in the AquaManager Communication menu or locally at the 5200A.  
Poll node using RS232 communication to upload configuration information 
including:  static IP, port, subnet, and gateway addresses.

 

-

Numbers between 0-255 are valid for each of the four (4) Gateway IP Address 
fields  

Port

Menus → System → Communications → Ethernet → Port

The default port number for the ethernet module is 10001.  Consult the network 
administrator when configuring this menu.

Note:

 

-

 AquaManager users should program the port number either by force serial 
port in the AquaManager Communication menu or locally at the 5200A.  

Configuring the 5200A

Poll node using RS232 communication to upload configuration information 
including:  static IP, port, subnet, and gateway addresses.

DNS Address

Menus → System → Communications → Ethernet → DNS

Domain Name Service (DNS) numbers are IP addresses that a workstation or server 
uses to refer to specific servers that resolve domain names to IP addresses.

Notes:

 

-

When DHCP is enabled, the serial to ethernet device will acquire SMTP and 
DNS addresses during initialization.

 

-

When DHCP is enabled, the DNS address is not updated at the IP address 
menu.

 

-

Numbers between 0-255 are valid for each of the four (4) DNS IP Address fields  

Email Addresses

Menus → System → Communications → Ethernet  

→ Email Address

 

     → 

Email 

Address

 

     → 

Email 

Address

 

     → 

CC/Email 

Address

Up to four email addresses can be configured for 

5200A emails.

  At a minimum, 

the first email address and the CC/email address must be configured. 

If the CC/

email address is not configured, 5200A alarm emails will not contain any alarm 
information.

  The email ‘from’ address will be the email address entered in the first 

Email Address

 menu. 

Notes:

 

-

See 

Send Test Email Msg

 - page 99 to verify proper configuration of ethernet 

menus.

 

-

On a network, both master and slave alarm emails are sent to the configured 
email addresses in the master.

 

-

Test the alarm email delivery by creating an alarm condition at the 5200A and 
verify the email(s) is received.

 

-

The CC/Email address must be configured when using 5200A email alarming.  
Specific alarm system information will not be sent if the CC/Email address 
menu is not configured with a valid email address. 

 

-

Use AquaManager to easily configure email addresses using the PC keyboard.  
See AquaManager on line help.

 

-

 If Autopoller is being used for AquaManager email alarming on a TCP/IP 
connection, it is strongly recommended that the 5200A email alarming using 
the serial to ethernet device be disabled.  When the ethernet device sends 

Configuring the 5200A

Содержание 5200A

Страница 1: ...YSI Incorporated 5200A Monitor and Control Instrument User Manual ...

Страница 2: ... 13 Input System Specifications 14 Component and System Non Input Specifications 16 2 Safety 19 THIS IS IMPORTANT 20 Warnings and Cautions 20 Warnings 21 Cautions 23 Health and Safety calibration solutions desiccant 23 Health and Safety Calibration Solutions 24 Calibration Solutions 24 3 Installation Wiring 25 Hardware Installation 26 Step 1 Install 5200A 27 Location Considerations 27 Mount the 52...

Страница 3: ...o Calibrate Conductivity Sensor 78 DO 80 Directions to Calibrate DO Sensor Sat Value 80 Directions to Calibrate DO Sensor mg L Value 82 ORP 83 Directions to Calibrate ORP Sensor 83 pH 84 Directions to Calibrate pH Sensor 84 Local vs Remote Instruments 86 System Menu 86 Adjust Contrast 87 BackLight Timer 88 Table of Contents Buzzer 88 Communication 89 Email Alarming 90 Ethernet 92 Node Network 96 S...

Страница 4: ...d Features 198 Software Installation 199 Table of Contents Getting started 199 AquaManager Windows 200 Explorer Window 200 Node Graph Window 201 Systems Management 202 Database Management 203 Autopoller 204 Mapping 205 AquaManager Alarm Emails 205 6 Maintenance 207 Maintenance 208 Probe Maintenance at the Deployment Site 208 Algae and Debris 208 Minimizing the Effect of Algae and Debris 208 Calibr...

Страница 5: ...25 Appendix 3 Menu Maps 226 Menu Map Key 227 Appendix 4 Declaration of Conformity 253 Appendix 5 Parts and Accessories 257 Appendix 6 SMS Messaging 261 Appendix 7 Warranty 262 Appendix 8 Contact Us 263 Ordering and Technical Support 263 Service Information 263 Appendix 9 Recycling 264 Recycling 264 Battery Disposal 264 Index 265 Table of Contents ...

Страница 6: ...itor management tool via direct RS232 or TCP IP connection AquaManager is required to configure IOEM instruments on a network NEW NEW Introduction email alarming via TCP IP from instrument and or AquaManager local or TCP IP connection NEMA 4X IP65 enclosure See Product Specifications page 13 for complete details on all 5200A features A configuration log records any changes made to the 5200A setup ...

Страница 7: ...ogram includes an extensive help system which contains detailed information that is not provided in this manual This icon is used throughout the manual to indicate helpful information for Aqua Manager users Is used to bring attention to new 5X00 instrument and AquaManager features and functionality Chapter 6 Maintenance starting on page 208provides information on maintaining the 5200A system inclu...

Страница 8: ...E membrane 95 of reading in 36 seconds for 2 0 mil Teflon membrane Allow approximately 10 15 minutes after 5200A is powered on or the DO sensor is serviced for the polarographic sensor to stabilize Introduction Flow requirements minimum flow rate of 3 inches per second or 7 62 cm second for 2 0 mil PE membrane 6 inches per second or 15 24 cm second for 2 0 mil Teflon membrane Other Automatic salin...

Страница 9: ...onics ARM7 embedded micropro cessor DSP digital signal process ing Digital processing of 5200A information ensures accurate and repeatable readings Introduction Firmware Feature Specification Flash Memory Firmware field upgradable with local PC connection Data Logging non volatile data log memory storage of 3750 records sensor log 1000 records event log 1250 records calibration log 500 records Con...

Страница 10: ...YSI 5200A 18 This page left intentionally blank 2 Safety IMPORTANT safety information Read this chapter before installing 5200A components and peripheral devices ...

Страница 11: ...nes de sécurité ne sont pas suivies Safety CAUTION RISK OF DANGER This symbol identifies installation and operation procedures that can result in personal injury or damage to equipment if safety information is not followed These symbols appear in the left margin of the page to highlight safety information as it applies to a particular installation or operation step A complete list of all safety ca...

Страница 12: ...terre WARNING Do not overload relays Verify that the surge current at startup does not exceed the relay load ratings Be familiar with all safety information regarding installing and servicing peripheral devices Safety AVERTISSEMENT ne surchargez pas les relais Vérifiez que la surtension de démarrage ne dépasse pas la capacité de charge nominale du relais Prenez con naissance de toutes les consigne...

Страница 13: ... page 61 CAUTION It is essential that all low voltage wiring including sensor wiring be run in a separate cable or conduit from high voltage wiring Health and Safety Calibration Solutions Calibration Solutions CAUTION Reagents used to calibrate and check this instrument may be haz ardous to your health Some calibration solutions may require special handling Refer to the Material Safety Data Sheet ...

Страница 14: ...ard and lower board assembly necessary tools for cutting mounting holes in mounting brackets rail mount and or control panel panel mount 5 32 Allen wrench panel mount only electric drill and bits for mounting 5200A panel or rail and for drilling rubber grommets in bulkhead fittings small flat head screwdriver to terminate wires on the I O board s plug gable terminal strips wrenchtotightenthebulkhe...

Страница 15: ...oles in the mounting brackets to fit the u bolts Use the pre drilled metal plate as a template 2 Fasten the mounting brackets to the back of the 5200A with the mounting screws as shown in figure 3 2 3 Tighten the screws securing the brackets to the 5200A 4 Place the u bolts around the rail securing the 5200A to the pipe or rail by feeding through the pre drilled holes on the mounting brackets as s...

Страница 16: ...e front panel out away from the IDC header figure 3 5 Installation and Wiring Figure 3 5 3 Remove and retain the four screws that secure the display board into front panel enclosure figure 3 6 The display board is mounted on panel that is attached to 5200A front panel The I O Board wiring diagram is located on the display board panel figure 3 6 4 Carefully lift out the display board and remove the...

Страница 17: ...200A front panel to the frame using mounting screws Follow procedures provided at Close Front Panel page 40 to secure 5200A and protect internal electronics 14 Tighten the screws securing the 5200A to the panel Install the Weather Shield Install the weather shield for outdoor installations The weather shield can be used with either a surface or a rail mount The weather shield kit model number 6505...

Страница 18: ...ocation that is free from debris e g algae ideally at a 45 angle from vertical position and directed with the flow figure 3 10 Installation and Wiring Figure 3 10 in awell mixed free flowing area midstreamand mid depth typically gives representative readings the probe assembly and cable are fully submersible up to the cable connector submersed at all times so liquid level fluctuations do not expos...

Страница 19: ... after servicing the DO sensor for the polarographic DO sensor to stabilize Installation and Wiring Figure 3 12 shows the external parts of the YSI 5562 probe assembly Figure 3 12 Wiring Information System components must be wired correctly to ensure reliable performance and accurate data collection Directions are provided in this section for wiring all com ponents and peripheral devices PCBs Ther...

Страница 20: ...5cm and 1 3 8 9525cm located at the bottom of the 5200A enclosure provide watertight entry points for 5200A system wiring The probe cable assembly connector is located below the bulkhead fittings figure 3 13 Rubber grommets must be pushed out of the compression fitting housing and drilled for wiring installation The drill bit diameter should be slightly smaller than the wire diameter so that a wat...

Страница 21: ...sure that ribbon cable is not trapped in the gasket channel before inserting mounting screws 6 Tighten mounting screws making sure not to cross thread The screws are stainless steel and the receiving threads are brass Do not over tighten WARNING The 5200A utilizes sensitive solid state devices that can be damaged by static shock Installers must observe accepted ESD Electro Static Discharge procedu...

Страница 22: ... version can be powered by either AC or DC power If the AC version is properly wired and configured for both AC and DC power and AC power fails the power switches to 12VDC If DC voltage drops below a user defined safe operating range an alarm occurs CAUTION At 120VAC the 5200A draws 25 watts 0 2 amps Use wiring suitable for that load following all safety information and local electrical codes Back...

Страница 23: ...n used as back up power source Installation and Wiring Power supply voltage above 16 5 VDC may permanently damage the 5200A When back up voltage falls below 9 0 volts the 5200A ceases to operate properly Some switching DC power supplies not supplied by YSI may result in noisy readings Directions to Wire DC Power DC Backup Power WARNING Disconnect external power to the unit before wiring Follow all...

Страница 24: ...figure 3 20 Directions to Wire Relay Outputs WARNING Disconnect external power to the unit before wiring If any of the relay contacts are connected to a hazardous live circuit ALL contacts on ALL relays must be considered hazardous live and appropriately protected from user contact outside the 5200A enclosure AVERTISSEMENT déconnectezl alimentationexternedel unitéavantd effectuer le câblage Si un ...

Страница 25: ...f applications including level switch pressure switch and or an external instrument with an analog recorder output Aux input wires are terminated at location K figure 3 21 See 5200A I O board wiring diagram on inside of front panel for identification of aux system number and pin position See Digital Input example figure 3 22 and Analog Input example figure 3 23 Notes All aux inputs have input prot...

Страница 26: ...ux Digital Input 1 Install aux digital device according to manufacturer s instructions 2 Connect switch wires to Aux Input 1 or 2 Connect one wire at G at K Connect second wire to 1 or 2 at K Float Switch Auxiliary Input Connector CAUTION Do not input external voltage Figure 3 22 Wire Aux Analog Input 1 Install analog instrument according to manufacturer s instructions 2 Connect analog instrument ...

Страница 27: ...with AquaManager and Legacy 5200 data will be stored in the same database as 5200A 5400 5500D 1 5500D 2 and 5500D 4 data Network traffic speed operates at 230 KB and is not user selectable Remove network terminal strip from any networked slave that is not powered Network rewiring is required if a stub see next note is created when a slave is taken off the network See valid network configuration fi...

Страница 28: ...ves as follows Wire Color Terminal solid blue T white with blue stripe T solid orange R white with orange stripe R green Communications Common C Figure 3 26 is a wiring diagram for the most common 5200A network configuration where a master 5200A is the first physical device in the network Figure 3 26 6 Wire all network terminal strips prior to network testing but only con nect a network terminal s...

Страница 29: ...wn above connect terminal strip to master and outer most slaves slaves 1 and 4 to begin network testing Testing in above graphic would occur first with slaves 1 and 4 and then continuing by testing slave device 2 or slave device 3 until all network wiring is tested Use below network wiring testing method when master is not first physical device on network Use below network wiring testing method wh...

Страница 30: ...ard to PC using RJ45 to DB9 adapter Directions to Wire Direct RS232 PC Connection WARNING Disconnect external power to the unit before wiring AVERTISSEMENT déconnectezl alimentationexternedel unitéavantd effectuer un câblage quelconque 1 Perform steps 1 4 of 5200A installation and steps 5 6 and 7 as required for the application 2 Open front panel page 40 Installation and Wiring 3 Feed direct conne...

Страница 31: ...entations on the cable con nector at the bottom of the YSI 5200A figure 3 30 3 Hold the cable firmly against the cable connector then turn the locking mechanism clockwise until it snaps into place Remove the cable from the instrument by turning the cable connector counterclockwise until the cable disengages from the instrument Installation and Wiring Figure 3 30 Notes Calibrate sensors prior to us...

Страница 32: ...e steps below to prevent damage to the electronic components and to extend the life of the 5200A system 1 Place solid rubber grommets in bulkhead fittings that have no electrical connections 2 If using optional conduit fittings YSI p n 065926UL in place of bulkhead fittings industrial encapsulant YSI p n 065921 conduit sealer must be used to prevent moisture from entering the 5200A enclosure Apply...

Страница 33: ...YSI 5200A 64 4 Configuring 5200A Systems Front panel keys Run Screen Navigating menus Menu structure Configuring 5200A systems This page left intentionally blank ...

Страница 34: ...ude configuration of IOEM slave and channel to be used for a sensor system output AquaManager includes software checks that help to validate IOEM 4 20mA output assignment configuration Front Panel Keys There are seven 7 5200A front panel keys figure 4 1 Use and keys to scroll and highlight menu lists and to scroll through multiple Run Screens Use key to select and enter a highlighted submenu item ...

Страница 35: ...r up the Run Screen is displayed immediately after the YSI splash screen the YSI splash screen appears for approximately 2 seconds Icons displayed at the Run Screen represent individual and systemwide conditions See Run Screen Icons page 70 Run Screen and sensor display formats are user selectable See Display Settings page 122 and Sensor Setup Menus page 146 Notes The Run Screen must be displayed ...

Страница 36: ...ion and or factory resets are restored after 30 seconds of completing Svr hold calibration and or factory resets For exceptions see menu specific information in this chapter Configuring the 5200A With alarms enabled alarm icons appear at the systemwide location and individual system location regardless if a relay is assigned to the sensor alarm or general alarm system ICONS Systemwide Significance...

Страница 37: ... screen formats are very intuitive Menus are structured in hierarchical fashion See Appendix 3 Menu Maps beginning on page 226 For example figure 4 3 illustrates the menu path to configure data logging interval Configuring the 5200A RunScreen Menus System DataLogging DataLogging DataLogging Enabled 1Hour LoggingInterval Timeunits RunScreen Menus SystemMenu DataLogging LoggingInterval Menu Hierarch...

Страница 38: ...nu All system configuration is done through this menu The four Main Menu submenus are Calibration System Sensor Setup and Timers Calibration Menu Sensors must be user calibrated to ensure accurate measurements Calibrate the sensors in the Calibration Menu Entering the Calibration Menu de energizes all active water sensor control and alarm relays There is a 30 second hold off period for control and...

Страница 39: ...e calibration menu Alarm systems are not reset until is pressed to return the instrument to the run screen Getting Ready to Calibrate Use the calibration storage cup figure 4 5 for all 5562 sensor calibrations To avoid cross contamination of solutions rinse the calibration storage cup between calibra tions Additionally rinse each sensor with a small amount of calibration solution that can be disca...

Страница 40: ...uctivity sensor is fully immersed in the solution figure 4 5 page 77 5 Gently move the probe module up and down to remove any air bubbles trapped in the conductivity sensor vent hole 6 Screw the calibration storage cup onto the threads of the probe module 7 Enter conductivity calibration menu Menus Calibration Conductivity 8 Allow at least one minute for the temperature to equilibrate Configuring ...

Страница 41: ... If not using a Conductivity sensor or if the conductivity sensor is disabled enter the salinity ppt value of the water to be monitored in DO Sensor Setup menu This will result in accurate DO mg L readings Menus Sensor Setup DO ppt Configuring the 5200A 5 Enter the local elevation in the DO Sensor Setup menu if not already configured Menus Sensor Setup DO Elevation 6 Follow these instructions to c...

Страница 42: ...plete the calibration OR press to cancel the calibration without saving 9 Use the arrow keys to select numbers on the numeric keypad enter the known DO value in mg L Press to confirm each number selection 10 Press to confirm the entered value OR press to abort the calibration without saving any changes Configuring the 5200A 11 Press to save the calibration and return to the Run Screen 12 Rinse sen...

Страница 43: ... storage cup on to the threaded end of the probe module 7 Enter pH calibration menu Menus Calibration pH 2 Point Cal recommended OR Menus Calibration pH 1 Point Cal 8 Allow at least one minute for temperature equilibration Configuring the 5200A 9 After one minute verify that the pH and temperature values show no significant change for approximately 30 seconds Then press to continue the calibration...

Страница 44: ...ity such as datalogging interval and general alarm settings Use system Aux and E Aux menus to configure Aux and E Aux input type display format and system name and suffix Use E Aux menu to configure IOEM slave address and channel assignment for corresponding E Aux system see page 107 Systemsubmenusareshownbelow Press attheRunScreentoentertheMain Menu Use to scroll and highlight a System submenu Pr...

Страница 45: ...ld off period The General Alarm must be enabled for the buzzer to sound Use the Buzzer Menu to enable or disable the audible alarm When enabled the buzzer will sound until one of the four bottom softkeys on 5200A front panel is pressed From the Run Screen press one of the following softkeys Configuring the 5200A to reset the General Alarm Resetting the General Alarm silences the buzzer de energize...

Страница 46: ...ll report the 5200A serial number and the default system names regardless if the names are user configured Configuring the 5200A Aux digital closed alarm is reported as 0 00 aux digital open alarm is reported as 1 00 Aux analog alarm emails are reported in 0 00 resolution regardless of the display format resolution See General Alarm page 128 and Sensor Setup Control modes and alarms page 149 for i...

Страница 47: ...s suspended This could potentially delay any AquaManager alarm emails from being sent Configuring the 5200A To disable the serial to ethernet device from sending alarms clear all four email addresses from the Communication Ethernet menus Clear the email addresses by using the Spc space key on the numeric keypad Save change at numeric keypad and press to save configuration and return to Run Screen ...

Страница 48: ...anager Communication menu or locally at the 5200A Configuring the 5200A Poll node using RS232 communication to upload configuration information including static IP port subnet and gateway addresses DNS Address Menus System Communications Ethernet DNS Domain Name Service DNS numbers are IP addresses that a workstation or server uses to refer to specific servers that resolve domain names to IP addre...

Страница 49: ...ith at least one slave are physically connected using RS485 protocol see page 52 for additional information Only the master node is configured for serial or ethernet module communication Configuring the 5200A On a network with at least one slave the master continuously queries enabled slaves on the network The master is the access point for the entire network This includes AquaManager communicatio...

Страница 50: ...k wiring instructions beginning on page 52 Repeat network configuration directions starting at step 8 until network wiring for master and all slaves has been tested Configuring the 5200A Notes An Event and General alarm if enabled will occur if after ten queries an enabled slave does not respond to the Master Configuring a 5200A as a Master overrides any slave configuration that had been previousl...

Страница 51: ...twork menu Menus System Communications Network Baud Rate 2 Press or to scroll and highlight a selection 3 Press to confirm selection 4 Press to save configuration and return to Run Screen Configuring the 5200A Force Serial Port Menus System Communications Force Serial Port Enable the Force Serial Port when the 5200A is communicating via RS232 direct to a PC and when the 5200A has a serial to ether...

Страница 52: ...g range is installed and configured Configuring the 5200A Digital Menus System Configure Aux Aux 1 2 Input Type Digital Use the digital input when monitoring an external device to control or alarm when the contacts of the external switch are open or close A common application would be to detect high or low water levels using a float switch Notes Suffix Min Max Input Scale Min Input Scale Max and D...

Страница 53: ...d for scaling the input value received from an analog aux input The min and max values may be configured to correspond to the minimum input level i e 0VDC or 4mA and maximum input level i e 1VDC 5VDC or 20mA The Min value must be less than Max value Example when using a total dissolved gas pressure sensor 0 5VDC input type enter 400 for min value The 5400 will display 400 when the input value is 0...

Страница 54: ...9 2 Enter Aux menu Menus System Configure Aux Aux 1 2 3 Use and to scroll and highlight submenus 4 Press to select 5 Press to save configuration 6 Go to Sensor Setup Menus Sensor Setup Aux 1 2 page 162 to enable and configure set points control alarm relays and hold off time 7 Press to save configuration Configure E Aux Menus System Configure E Aux 1 8 5200A instruments have eight E Aux systems E ...

Страница 55: ...es can also be configured at Menus System Name Devices Sensors Name E Aux Instrument Menus System Configure E Aux E Aux 1 9 Instrument Device Address menu opens Configuring the 5200A Select the IOEM slave device address whose input will be used as an input signal for this E Aux system Use to scroll and highlight IOEM Slave device address Press to select Press to save settings and return to Run Scr...

Страница 56: ...h Configuring the 5200A Notes IOEM input channel modes can only be configured using AquaManager See AquaManager online help for directions to configure IOEM channel input mode digital 0 1V 0 5V 4mA 20mA temperature Suffix Min Max Input Scale Min Input Scale Max and Display Format are not available for digital inputs In the 5200A sensor log aux digital closed is logged as Aux 0 00 Aux digital open ...

Страница 57: ... input The min and max values may be configured to correspond to the minimum input level i e 0VDC or 4mA and maximum input level i e 1VDC 5VDC or 20mA The Min value must be less than Max value Configuring the 5200A Example when using a total dissolved gas pressure sensor 0 5VDC input type enter 400 for min value The 5400 will display 400 when the input value is 0VDC Set the max value to correspond...

Страница 58: ...nel mode to 0 1v 0 5v or 4 20mA 4 Enter E Aux menu 5 Menus System Configure E Aux E Aux 1 8 6 Use and to scroll and highlight submenus to configure Configuring the 5200A 7 Press to select 8 Configure E aux system name page 108 instrument page 108 channel page 109 input type page 110 suffix page 112 min max page 112 scale min scale max page 113 and display format page 114 menus 9 Press to save conf...

Страница 59: ...l and highlight submenus 3 Press to select 4 Enable and configure submenus 5 Press to save configuration and return to Run Screen Press to view the 25 most recent sensor logs Notes Temperature values are stored in C regardless of display format Aux digital closed is logged as Aux 0 00 Aux digital open is logged as Aux 1 00 The 5200A sensor log records 0 00 resolution for aux analog inputs regardle...

Страница 60: ...stem name Event logs do not record relay number or user configured relay name Aux digital events will never display alarm regardless if alarms are enabled see below screen shot on right E Aux system event logs are stored at the local instrument whose E Aux system is being used and not at the device whose output is creating the event For example if an IOEM channel 2 whose slave address is 4 is conf...

Страница 61: ... has been energized it runs for the duration and does not reset based on changes to the 5200A date and time Example timer 1 event 1 is configured to come on at 9 00am for Configuring the 5200A 10 minutes Timer relay energizes at 9 00am At 9 05am the 5200A time is changed to 10 05am for daylight savings adjustment The timer relay will de energize after five additional minutes The 5200A time will be...

Страница 62: ...ions to the 5200A firmware Download new firmware using the Firmware Updater utility in AquaManager A serial RS232 connection is necessary to run the Downloader program The instrument firmware may become corrupted if any of the following occurs during a 5200A firmware update Firmware Updater utility is closed AquaManager is closed RS232 cable is removed from 5200A or PC com port power is disconnect...

Страница 63: ...oad this file into the Firmware Updater 7 Left click button Configuring the 5200A window opens 8 Select Yes and the following screens will appear On instrument On PC YSI 5200A 5400 5500 Bootstrap Loader screen Flash Programmer uploading firmware into 5200A Note If the YSI 5200A 5400 Bootstrap Loader screen does not appear at the in strument after above steps manually place 5200A in downloader at M...

Страница 64: ... or Could not find Unit messages indicate a communication problem between PC and 5200A Reconfirm Communication menu configuration com port settings and RS232 connections A power cycle will be required to access the Com munications menu from the Bootstrap Loader screen Place 5200A in downloader mode again and select yes to retry at Firmware Updater error message window If the upload is still unsucc...

Страница 65: ...x Sensor Setup page 157 for important aux control and alarm system information Notes The Run Screen must be displayed during normal operation All alarm functions 5200A alarm emails energizing of enabled alarm relays alarm Configuring the 5200A icons and buzzer are suspended in 5200A menus Alarm systems are reset when menus are exited to Run Screen The General Alarm system is disabled during system...

Страница 66: ... to Run Screen Configuring the 5200A 7 Test General Alarm Relay output at System Service Output Test page 141 or create a general alarm event to verify configured general alarm relay energizes Note The General Alarm does not create an event log or control message regardless if a General Alarm relay is enabled Name Devices Sensors Menus System Name Devices Sensors Names can be user configured for 5...

Страница 67: ...The instrument name is shown at relay enable menus for a local instrument only Certain menus i e configure aux display up to 18 characters of the device name is shown at the menu if the name exceeds 18 characters Configuring the 5200A Below are screen shots of Run Screen and system low alarm menu displaying user configured system name CATFISH NE Instrument and relay name conventions across a netwo...

Страница 68: ...elect 4 Enable and configure submenus 5 Press to save configuration and return to Run Screen Notes is not password protected icon displays at Run Screen when password function is enabled Power Fail Menu Menus System Power Fail In the event of AC power failure an AC version instrument s power switches to DC if properly wired The switch from AC to DC power is automatic and does not require 5200A con...

Страница 69: ...ral Alarm Serial Number Menus System Serial Number The serial number is displayed at the serial number menu The serial number is required when contacting YSI customer service The serial number is also necessary to configure AquaManager 5200A serial numbers begin with 53 followed by seven digits Serial numbers are generated at the factory and cannot be changed by the user Configuring the 5200A Serv...

Страница 70: ...to factory menus Relay names are reset at reset relays and reset all menus Perform sensor calibration after selecting Reset All and or Reset Sensors Configuring the 5200A Control icons and control menu messages are displayed for 30 seconds after pressing from reset to factory menus for any system that was active energized relay prior to the factory reset Reset All Menus System Service Reset To Fac...

Страница 71: ...ve configuration and return to Run Screen Output Test Menus System Service Output Test Use the Output Test menu to verify that local relays and remote device relays and IOEM 4 20mA output channels are wired and communicating correctly over the network Entering this menu turns off any active relays and disables any sensor aux and timer system relays from energizing regardless of value or condition ...

Страница 72: ...name has been user configured Channel 1 8 are always listed regardless if instrument selected is a 5200A or an REM which instruments have 4 relay channels and not 8 relay channels Configuring the 5200A 5 Scroll and select Relay or 4 20mA output type 6 4 20mAoutputstestanIOEM4 20mAoutputchannel For4 20mAoutput test configure a Milliamp value The Milliamp raange is 0 00 to 21 00 7 Select Yes at Ener...

Страница 73: ...ersion Menus System Version The Version menu contains information about the 5200A including display and control board firmware code version firmware compile date and time control board temperature AC and DC voltage and model number Notes Firmware version information is required when contacting YSI support The clock chip temperature range starts at 0oC Values 0oC are not valid numbers Configuring t...

Страница 74: ... system relay output pulldown menus This AquaManager table is not visible to the user An Example of configuring a 5X00 system control relay at an instrument versus using AquaManager is provided below The node network used in the example includes a master being a 5500D 04 and 4 slaves slave 2 being a 5500D 02 slave 4 being a 5400 slave 11 being a 5200A slave 16 being an REM NEW Configuring the 5200...

Страница 75: ...defaults and ranges One relay can be assigned to multiple systems It is essential that the relay configuration be verified in order to avoid conflict of operation of wired relay devices Assigning one relay to multiple systems can result in invalid operation Configuring the 5200A Control Mode Menus Sensor Setup Aux 1 Control Mode Aux 2 Control Mode Conductivity Control Mode DO Control Mode ORP Cont...

Страница 76: ...et Point Control Values Range low and Range high values set the acceptable operating range for the water system Control system s do not become active when value s are within acceptable control range See figure 4 7 page 151 Enabled control relays energize when the sensor reports a value the range low control value or range high control value Control relays are typically wired to devices used to rai...

Страница 77: ...h alarm range starts at 1 significant digit above high control value Configuring the 5200A Notes Configure sensor control relays using AquaManager see page 146 It is important to keep the 5200A at the Run Screen during normal opera tion Alarmfunctionality emailalarms activationofenabledalarmrelays alarm icons and buzzer is suspended when 5X00 is not at Run Screen Alarm icon s display at the Run Sc...

Страница 78: ...0A Autofix occurs when a high or low control value is entered that breaches the set point value Autofix changes the high or low control value by one least significant digit away from the set point value The set point value is never adjusted Example Entering 8 00 mg L as the range low value when the set point value is 8 00 mg L results in an auto fix of the control value The invalid control value i...

Страница 79: ...ontrol Mode A PID Propotional Integral and Derivative 4 20mA control mode system uses an IOEM 4 20mA output device to control the system The 4 20mA output control device is wired at an IOEM instrument see IOEM REM Safety and Installation Guide chapter 3 directions to wire 4 20mA outs for wiring directions and config ured using AquaManager see IOEM REM Safety and Installation Guide chapter 4 config...

Страница 80: ...ntrol configurations are all interrelated in the calculation of the control relay on time as the algothrium calculates the proper corrective action Configuring the 5200A PID PWM Gain control action Range 0 01 to 10 Gain is used to control the percentage of change in the output Output increases with greater gain A high gain results in a large change in the output for a given change in the error A g...

Страница 81: ...onfigured on 30 second hold No off event log is created when energized system relays de energize due to 30 second sensor hold off Control icons and control messages continue to display during the 30 second sensor system hold at the Run Screen regardless if relays are energized Aux and E Aux Hold Off non temperature aux systems Aux and E Aux Hold Off user configured is the length of time the contro...

Страница 82: ...uaManager see page 146 8 Optional Configure digital 4 20mA output page 178 9 Press to save configuration and return to Run Screen 10 Test system output device s at System Service Output Test page 141 or create an event to verify configured relay s energize Notes It is important to keep the 5X00 at the Run Screen during normal operation Alarm functionality email alarms activation of enabled alarm r...

Страница 83: ...gned to multiple 5X00 systems It is essential that the relay configuration be verified in order to avoid conflict of operation of wired relay devices If not configured properly assigning one relay to multiple systems can result in invalid operation of 5X00 E Aux system datalogs are not accessible at the 5X00 They must be viewed using AquaManager AquaManager identifies Aux analog events as control ...

Страница 84: ...00 systems It is essential that the relay configuration be verified in order to avoid conflict of operation of wired relay devices If not configured properly assigning one relay to multiple systems can result in invalid operation of 5X00 E Aux temperature values are not accessible at the 5200A Temperature readings can only be obtained using AquaManager Readings will be shown in the AquaManager dat...

Страница 85: ...onnect Probe assembly page 60 2 Wire relay output device s to local instrument or any networked 5X00 instrument page 46 AND OR 2 Wire relay output s device to REM see IOEM REM Safety and Installa tion guide Chapter 3 Step 4 Wire REM Relay Outputs Wire any output devices to be used for system 3 Enter Conductivity Sensor Setup menu Menus System Sensor Setup Conductivity 4 Use to scroll and highlight...

Страница 86: ...ed salinity is ALWAYS calculated by the conduc tivity sensor and this value is used to calculate DO mg L Disabling conductivity requires that a ppt value be entered in the 5200A DO sensor menu In this menu enter the salinity value of the water being moni tored The acceptable salinity input range is 0 50 ppt 5561 probe cable users should ALWAYS disable the conductivity system since there is no cond...

Страница 87: ...dless if DO range low 1 or DO range high 1 relays are also energized See 30 Second Sensor Hold Off page 160 ORP Menus Sensor Setup ORP Configure ORP sensor system Before configuring Conductivity system 1 See Use AquaManager to configure system inputs and outputs page 146 AND 2 See Control modes Set point Control Mode and Alarms page 150 and PID control mode 155 1 Connect Probe assembly 60 2 Wire r...

Страница 88: ...d when 5200A is not at Run Screen One relay can be assigned to multiple 5200A systems It is essential that the relay configuration be verified in order to avoid conflict of operation of wired relay devices If not configured properly assigning one relay to multiple sys tems can result in invalid operation of 5200A pH set point control and alarm values can be up to five 5 characters in cluding the d...

Страница 89: ... DO and temperature It is important to keep the 5X00 at the Run Screen during normal operation Alarm functionality email alarms activation of enabled alarm relays alarm icons and buzzer is suspended when 5X00 is not at Run Screen At sensor log Aux 1 1 00 is reporting open condition Aux 1 0 00 is re porting closed condition Do not enable aux digital alarms when the sensor is in the control alarm co...

Страница 90: ...onfigure ioem 4mA 20mA output to a 5X00 system bookmark Configure 4 20mA outputs at sensor system tabs in AquaManager 4 20mA con figuration fields are located at the bottom of all sensor system tabs AquaManager and the Sensor Setup Menu All Sensor Setup menus can be configured using AquaManager After polling the 5200A node use Systems Management to view and upload 5200A configuration Notes Always ...

Страница 91: ...e timer relay 1 is configured to start at 11 00 am for one hour Timer relay energizes at 11 00 am At 11 15 am the 5200A is put into downloader mode Timer 1 relay de energizes Timer 1 relay re energizes 30 seconds after power cycle following the firmware update at approximately 11 24 am The timer relay de energizes at 12 24 pm and not at 12 00 pm which would have been the original off time if the u...

Страница 92: ...l Sensor control reduces the amount of food dispensed if DO pH or temperature measurements are out of range per user defined configuration The FCR Feed Conversion Ratio feature automatically computes and increases the daily amount of food dispensed per FCR configuration Notes It is important that the 5200A be configured with valid data The feeder system will not operate properly if for example the...

Страница 93: ...t feed occurs by 11 59 pm 23 59 on Saturday since Sunday is a disabled day The next feed occurs at 12 00 am 0 00 on Tuesday This feed cycle would end at 01 00 on Tuesday No feeding occurs Monday because Monday is a disabled day The Feed timer will not operate properly if the start date is set prior to Janu ary 1 2007 Daily Weight Menus Timers Feed Smart Timer Feeder Daily Weight The daily feed amo...

Страница 94: ...hange Temp Low High Temp Change Changes in water conditions affect the amount of food fish eat which in turn affects fish growth With the sensor feature enabled the feed timer system will verify that DO temperature and pH values are within user configured ranges This verification is done immediately prior to starting each feed duration in a feed cycle If values are reported that fall outside the a...

Страница 95: ...time the feeder relay will energize 6 Press for feed timer relay to energize for configured run test time Countdown of relay on time is displayed 7 When run time expires the relay de energizes Enter the amount of food dispensed at the Measured Weight screen 8 Press to save settings and return to Run Screen Notes Since feeders and food size vary run several calibrations and enter the aver age weigh...

Страница 96: ...fy that the uploaded information is retained When configuration changes are uploaded using AquaManager at the same time configuration changes are being made by a user in the menus at the 5200A AquaManager uploads may not be saved depending on the timing of keystrokes at the 5200A The Run Screen must be displayed during normal operation If the 5200A is not at the run screen during AquaManager uploa...

Страница 97: ...ed Msg s Menu Calibration Sensor and Event logs contain 5200A system information The 5200A Sensor log stores 1000 records The Calibration log stores 500 records The Event log stores 1250 records Once the log memory is full the oldest records are over written with more recent records The number shown in at the Msg s menu reflects the total number of records in the log The 25 most recent records for...

Страница 98: ...sed and not at the device whose output is creating the event For example if an IOEM channel 2 whose slave address is 4 is configured as an E Aux temperature input for a 5200A slave 14 and a low tempera ture control relay output for this slave 14 is configured to a 5500 master the 5200A slave 14 and not the master 5500 records the low temperature control events Sensor Logs Enabled systems record se...

Страница 99: ...elay energized at service hold the relay will not reenergize after service hold expires regardless if timer time has not expired There is only one on time for all timer systems Entering Downloader mode places 5200A into Service Hold Inst Service Hold is displayed on any AquaManager map icon associated with an instrument in Service Hold AquaManager alarm emails are not sent for any alarm condition ...

Страница 100: ...ication is being installed In addition Vista users must enable UAC properties prior to AquaManager registration Go to Aquamanger exe file properties in the program file folder and check the box Run with Administrator Privileges AquaManager Additional System Recommendations Total RAM installed 64 Megs or greater 300 MB of free hard disk space latest versions of Microsoft including O S and Internet ...

Страница 101: ...figure system wide properties print tree and printer setup exit program cut copy and find node s AquaManager delete node or group sort nodes in group expand and collapse tree view access network log files insert manual event and manual data into node password administration launch autopoller generate reports manual database maintenance launch update firmware utility configure window display format...

Страница 102: ... configure node timer and feed timer systems view and configure most node systems 5200A system menu configure node mapping icons Notes Always manually poll the 5200A after uploading configuration changes and verify that the uploaded information is retained When configuration changes are uploaded using AquaManager at the same time configuration changes are being made by a user in the menus at the 5...

Страница 103: ...ayed when pH is in acceptable operating range a second icon is displayed when pH system is in control range when enabled and a third icon is displayed when pH system is in alarm range This provides a quick visual of system conditions at the PC Near real time Map is updated several times a minute as AquaManager constantly communicates with nodes during Autopolling Node mapping is available for dire...

Страница 104: ...ail to each email address configured in the Email Alarm List in the Node Properties window Test emails can be sent in the AquaManager Properties window under the Autopoller tab AquaManager 6 Maintenance Sensor Calibration Checks Sensor Maintenance Sensor Storage Charging DC Batteries AquaManager Database ...

Страница 105: ...Calibration Checks Maintenance The sensors are of high quality and should exhibit excellent performance in ex cess of the warranty period see page However the dissolved oxygen pH ORP and conductivity sensors will inevitably show some drift during deploy ment due to natural chemical changes to the reagents in the probes physical changes of the electrodes and or minor fouling of the sensor surfaces ...

Страница 106: ... proper operation NOTE This procedure does not include quantitative data taken with regard to either the temperature or conductivity sensors The temperature sensor only fails in very rare circumstances and if it does fail the temperature readings will seem Maintenance unreasonable for the current conditions In the unlikely event that the temperature sensor shows unusual and or jumpy readings it wi...

Страница 107: ...f after several hours you are still unable to calibrate contact YSI Customer Service Gold Cathode Cleaning Maintenance For correct sensor operation the gold cathode must be textured properly It can become tarnished or plated with silver after extended use The gold cathode can be cleaned by using 400 grit wet dry sand paper This should be done about once or twice per year Using the sand paper provi...

Страница 108: ...form the following additional procedure 1 Use a mild detergent solution in combination with the brush Dip the brush in the solution and insert it into each hole 15 20 times 2 Rinse the cell thoroughly in deionized or clean tap water 3 After cleaning check the response and accuracy of the conductivity cell with a calibration standard If this procedure is unsuccessful or if sensor performance is imp...

Страница 109: ...emove the pH or pH ORP sensor from the probe module 2 Seal the empty port with the provided port plug 3 Place the sensor in the storage vessel plastic boot or bottle that was on the sensor during shipment The vessel should contain a solution which is 2 molar potassium chloride or pH buffer 4 Note Make certain that the vessel is sealed to prevent evaporation of the storage solution DO Sensor The DO...

Страница 110: ...ndix 1 Unpacking and Inspection Appendix 2 Troubleshooting Appendix 3 Menu Maps Appendix 4 Declaration of Conformity Appendix 5 Parts and Accessories Appendix 6 SMS Messaging Appendix 7 Warranty Appendix 8 Contact and Service Information Appendix 9 Product Recycling ...

Страница 111: ...e damaged or missing contact YSI or your YSI representative im mediately Unpacking and Inspection Appendix 2 Troubleshooting Sensor Troubleshooting When troubleshooting sensors disable the control alarm relays Verify 5200A wiring and configuration Issue possible cause possible solution inaccurate or fluctuating sensor values improper placement of probe assembly See Location Considerations Step 2 L...

Страница 112: ...ion change 30 seconds delay see page128 and page132 peripheral device is wired incorrectly See Wire Relays page 46 and Test Relays page48 Troubleshooting Sensor Troubleshooting continued Issue possible cause possible solution relays are not enabled for control alarm timer system Verify menu configuration relay enable for control alarm timer system See sensor system enable page128 See timer system ...

Страница 113: ...d time stamp than the 25 most current data log records available at 5200A sensor log See Data Logging page102 Troubleshooting Firmware Updater Troubleshooting Issue possible cause possible solution Device timed out error incorrect configuration in 5200A communication menu See Device Timed Out er ror page 112 incorrect wiring of RS232 connection See Device Timed Out er ror page 112 5200A does not g...

Страница 114: ... to enter communication menu 5 Scroll if necessary to highlight ethernet menu 6 to enter ethernet menu 7 Scroll down if necessary to highlight IP address menu 8 to enter IP address menu numeric keypad is displayed 9 Configure the IP address using numeric keypad 10 after entering IP address 11 to save configuration and return to run screen Menu Maps Menu Map Key The following conventions are used i...

Страница 115: ...Adjust Contrast arrow keys to adjust enter to exit and save Buzzer Disabled BackLight Timer Enabled Time 30 Sec 1 255 Time Units Sec Sec Min Hours Run Screen Menus System Menu Adjust Contrast Buzzer and BackLight Timer Run Screen Menus Calibration Conductivity Enabled User Cal Value 1 200 µ S 1 2000µS 1 20mS 1 200mS DO Enabled SAT mg l User Cal Value 0 1 to 60 ORP Enabled User Cal Value 2000 to 20...

Страница 116: ... Test Email Msg Not Available Email test has been placed in the queue Email Retry Delay Not Available 15 1 255 Time Units Not Available Sec Min Hours Baud Rate Default Baud Rate 9600 14400 19200 38400 57600 115200 Force Serial Port Disabled Menu Maps System Configure AUX Aux 1 2 Disabled Name Probe Name Input Type 4 20ma Digital 0 v 0 5v 4 20ma Suffix Min 0 10000 to 10000 Max 1000 10000 to 10000 I...

Страница 117: ...20 10000 to 10000 Input Scale Min 4 00 suffix 10000 to 10000 Input Scale Max 20 suffix0 10000 to 10000 Display Format 0 0 0 0 0 00 Run Screen Menus System Menu E Aux Aux analog only not available for aux temperature or digital Menu Maps System Data Logging Data Logging Data Logging Enabled 1 Hour Logging Interval Time units Sec Min Hours Event Logging Enabled Clear Logs Data Events Data and Events...

Страница 118: ...07 Year 2007 2007 to 2099 Month January January February March April May June July August September October November December Day 1 1 t 31 1 to 31 Set Time Format 12 Hour 12 Hour 24 Hour Set Time Hours 7 Minutes 0 Seconds 47 Mode PM AM PM Menu Maps Run Screen Menus System Menu Display Settings System Display Settings Display Format 1x1 1x1 1x2 2x2 2x3 Page Change Speed 10 Sec 1 65535 Run Screen Me...

Страница 119: ...sabled Power Fail AC Monitor Not Available Low Battery Monitor Not Available Low Battery Trigger Not Available 9 15 Power Fail System must be enabled to have access to these menu items Menu Maps Run Screen Menus System Menu Serial Number System Serial Number 53 1122330 Run Screen Menus System Menu Service Hold System Service Hold Disabled Service Hold Enabled Service Hold Off 5 Min 1 to 255 Time U...

Страница 120: ...Sensor Setup Aux1 2 E Aux 1 8 Digital Hold Off 15 Sec 1 255 Time Units Sec Sec Min Hours Control Alarm Relay Disabled Digital Disabled Instrument Instrument Device Address Local Machine Master Slave 1 31 Relay Unassigned Relay 1 8 Output 4 20ma Disabled Aux X disabled Instrument Channel Min 0 0 Max 100 0 l all menus must be configured using AquaManager Output Scale 4 0mA Output Scale Max 20 00 mA ...

Страница 121: ...mA only PID Reset Interval 20 00 PID PWM PID 4 20mA only PID Gain 2 00 PID PWM only PID Relay Disabled E Aux 1 Disabled Instrument Instrument Device Address Local Machine Master Slave 1 31 Continued from prior page Aux and E Aux Analog all control modes unless indicated at column 2 Slave 1 31 Relay Unassigned Relay 1 8 PID 4 20mA only PID Output 4 20ma Disabled Aux X disabled Instrument Channel Mi...

Страница 122: ...s Local Machine Master Master Slave 1 31 Relay Unassigned Relay 1 8 Set Point 8 00 mg l 5 0 60 00 mg l PID PWM PID 4 20mA only Control Up Down Rising Rising Falling PID PWM PID 4 20mA only PID Mode mg l Sat mg l PID PWM PID 4 20mA only PID Interval 100 00 Seconds PID PWM PID 4 20mA only PID Reset Interval 20 00 Seconds PID PWM PID 4 20mA only PID Gain 2 00 PID PWM only PID Relay Disabled DO Disabl...

Страница 123: ... Reset Interval 20 00 PID PWM PID 4 20mA only PID Gain 2 00 Menu Maps PID PWM only PID Relay Disabled Temperature Disabled Instrument Instrument Device Address Local Machine Master Slave 1 31 Relay Unassigned Relay 1 8 PID 4 20mA only PID Output 4 20ma Disabled Temperature disabled Instrument Channel Min 0 0 Max 100 0 Output Scale 4 0mA all menus must be configured using AquaManager Continued from...

Страница 124: ...M PID 4 20mA only PID Reset Interval 20 00 PID PWM PID 4 20mA only PID Gain 2 00 Menu Maps PID PWM only PID Relay Disabled Temperature Disabled Instrument Instrument Device Address Local Machine Master Slave 1 31 Relay Unassigned Relay 1 8 PID 4 20mA only PID Output 4 20ma Disabled Conductivity disabled Instrument Channel Min 0 0 Max 100 0 Output Scale 4 0mA Output Scale Max 20 00 mA all menus mus...

Страница 125: ...ly Control Up Down Rising Rising Falling PID PWM PID 4 20mA only PID Interval 100 00 PID PWM PID 4 20mA only PID Reset Interval 20 00 Menu Maps PID PWM PID 4 20mA only PID Gain 2 00 PID PWM only PID Relay Disabled Temperature Disabled Instrument Instrument Device Address Local Machine Master Slave 1 31 Relay Unassigned Relay 1 8 PID 4 20mA only PID Output 4 20ma Disabled Temperature disabled Instr...

Страница 126: ...nuous Daily Weight 0 oz 1 to 100000 Daily Feedings 3 1 255 Start Date 01 01 2007 Year 2007 2007 2099 Month January Jan Dec Day 1 1 31 Run Screen Menus Timers FeedSmartTimer 1 1 31 Start Time 12 00 00 AM Hours 12 1 12 Minutes 0 1 59 Seconds 0 1 59 Mode AM AM PM End Date 01 01 2007 Year 2007 2007 2099 Month January Jan Dec Day 1 1 31 End Time 12 00 00 AM Hours 12 1 12 Minutes 0 1 59 Seconds 0 1 59 M...

Страница 127: ... Conformity The undersigned hereby declares on behalf of the named manufacturer under our sole responsibility that the listed product conforms to the requirements for the listed European Council Directive s and carries the CE mark accordingly Manufacturer YSI Incorporated 1725 Brannum Lane Yellow Springs OH 45387 USA Product Name 5200A Model Numbers Instrument Accessory 5200A Conforms to the follo...

Страница 128: ...00A Model Numbers Instrument Accessory 5200A Conforms to the following Standards FCC 47 CFR Part 15 2008 Radio Frequency Devices ICES 003 2004 Digital Apparatus Supplementary Information Tested using ANSI C63 4 2003 and CAN CSA CEI IEC CISPR 22 02 Signed Lisa M Abel Date 24 July 2011 Title Director of Quality Declaration of Conformity The undersigned hereby declares on behalf of the named manufact...

Страница 129: ... technician for additional suggestions The user may find the following booklet pre pared by the Federal Communications Commission helpful How to Identify and Resolve Radio TV Interference Problems This booklet is available from the U S Government Printing Office Washington D C 20402 Stock No 0004 000 00345 4 FCC Required Notice Appendix 5 Parts and Accessories Replacement Part Part Number and Desc...

Страница 130: ...nt Compression Plugs Large 605229 2 each included with instrument Compression Plugs Small 605804 1 each included with instrument Conduit fittings 065926UL For optional conduit mount industrial encapsulant required Conduit Sealer 065921 industrial encapsulant require for above item Desiccant pack replacement 006506 included with instrument DO sensor reconditioning kit 052380 includes 400 grit sandi...

Страница 131: ...e of your email address or cell phone information is 49 characters This should be large enough to cover most email addresses Below is a list of major USA Cellular and Pager companies that support sending Text messages to a Cell Phone or pager device via email xPort Ethernet solution If your carrier is international or is not listed here please visit http www notepage net smtp htm for a more compre...

Страница 132: ...r than YSI of any defective or improper component or part in servicing or repairing the product 6 modification of the product in any way not expressly authorized by YSI THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE YSI S LIABILITY UNDER THIS WARRANTY IS LIMITED TO REPAIR OR REPLACEMENT OF THE PROD...

Страница 133: ... instrument contains a manganese dioxide lithium coin cell battery that must be in place for continuity of power to memory devices on the board This battery is not user serviceable or replaceable When appropriate an authorized YSI service center will remove this battery and properly dispose of it per service and repair policies Recycling Index Index Symbols 5X00 instruments meaning and usage 12 30...

Страница 134: ...thernet 92 Index SMS messaging 96 force serial port 101 network 96 RS232 baud rate 100 send test email 99 Conductivity temperature compensation 168 timed and normal control 168 Conductivity calibration 78 Configuration chapter 65 Configuration log 116 contactor wiring See Wiring contactor Contact Us 263 Control board 41 Control menu 192 Control modes 149 PID PWM control 161 PID PWM control actions...

Страница 135: ...tallation 60 SMS messaging 96 Event logging 118 Event log view 194 Explorer window AquaManager 200 F Factory defaults 226 227 277 fcr feed timer 185 Feed Smart Timer 182 biomass 185 calibrate 188 Index daily feedings 185 daily weight 186 fcr biomass 185 daily weight 186 fcr factor 186 feed biomass 186 feed mode continuous 183 timed 184 sensors 187 DO pH temperature low high change 187 Firmware Upd...

Страница 136: ...ersus remote machine 86 Logs calibration log 78 clear logs 119 Configuration log 116 event log 118 sensor log data log 116 M Maintenance AquaManager database maintenance 217 Membrane replacement Index DO 5561 36 Menus Calibration 75 conductivity 78 DO mg L 82 sat 80 ORP 83 pH 84 Control 192 Menu maps 226 menu map key 227 Msg s menu 193 Sensor setup Aux analog 0 1V 0 5V 4 20ma 163 temperature 165 c...

Страница 137: ...tup menu 173 output and relay test 141 over See Sensors over and under values P Panel mount 5200A 29 Parts and accessories 257 Index Password menu 132 PCBs printed circuit boards 37 pH pH Calibration 84 pH sensor setup 174 Port ethernet menu 94 Port plugs 77 Power fail menu 135 Power wire 43 AC 43 DC and backup 44 view current power 145 Probes calibration 75 connect probe assembly 60 locate and in...

Страница 138: ... Reset to factory SMS messaging 96 SMS messaging formats 261 Softkeys 67 Specifications inputs aux 14 sensors 14 systems non input 16 17 communication 17 Index ethernet module 17 RS232 17 firmware 17 hardware relays 16 Stub network wiring 52 Submenu screen types 74 Subnet mask ethernet menu 94 Surface mount 5200A 28 Surge and lightning protection 61 Systemwide event 118 T Table of Contents 3 6 Tec...

Страница 139: ...es Unpacking and inspection 220 using to configure system inputs and outputs 146 V Version firmware 144 W Warranty 262 Weather shield 33 Wiring 37 55 aux auxiliary inputs analog instrument 51 digital instrument 51 bulkhead fittings 38 communication equipment 57 RS232 58 control board 41 PCBs 37 power AC 43 DC 44 backup 44 probe assembly 60 relays outputs 46 Item 605876 Rev F Drawing A605876 May 20...

Отзывы: