<9. Connection Device Type>
9-9
IM 01W03D02-01EN
Integral
indicator
NAMUR
NE107
category*
1
Bit
Diagnostic
Status
Diagnostic
Status Detail
Cause
Release/
recovery
conditions
(except
restart) *
2
Output
Operation
Action
AL.50
C
25
Installation,
calibration
problem
DEVICE
CONNECTION
ERR
Connection
error between
the Modbus
device and
FN310
None
Output
value: Hold
previous
value
Output
status: BAD
Configuration
Err
Check
the wiring
between
the Modbus
device and
FN310
AL.52
DEVICE
PUBLISH
INTERVAL
ERR
Delay of
SENCOM
start-up time
due to the low
temperature
of the
measurement
target
Change the
update time
corresponding
to the
temperature
characteristics
of SENCOM
Check the
update
time and
temperature
characteristics
of SENCOM.
For the
temperature
characteristics
of SENCOM,
refer to the
user’s manual
of SENCOM.
AL.60
C
24
Out of service AI1 OUT OF
SERVICE
AI1 block is O/S
mode
Recover when
the mode
target of alert
block is other
than O/S
Output
value: Hold
previous
value
Output
status: BAD
Configuration
Err
Check the AI1
block setting
AI2 OUT OF
SERVICE
AI2 block is O/S
mode
Check the AI2
block setting
AI3 OUT OF
SERVICE
AI3 block is O/S
mode
Check the AI3
block setting
AI4 OUT OF
SERVICE
AI4 block is O/S
mode
Check the AI4
block setting
AL.61
C
17
Simulation is
active
AI1
SIMULATION
ACTIVE
Simulate Switch
of AI1 block is
enabled
Recover when
the Simulate
Switch of
target block is
set to disable
Output
Simulate
Value of AI1
block
Check the AI1
block setting
AI2
SIMULATION
ACTIVE
Simulate Switch
of AI2 block is
enabled
Output
Simulate
Value of AI2
block
Check the AI2
block setting
AI3
SIMULATION
ACTIVE
Simulate Switch
of AI3 block is
enabled
Output
Simulate
Value of AI3
block
Check the AI3
block setting
AI4
SIMULATION
ACTIVE
Simulate Switch
of AI4 block is
enabled
Output
Simulate
Value of AI4
block
Check the AI4
block setting