<5. Wiring>
5-3
IM 01W03D02-01EN
5.3.2 Connection of FN110
To install FN110 with remote antenna cable,
follow the procedure below.
Remove the battery pack from FN310 before
connecting the remote antenna cable.
1. Connect the FN110 and the FN310 with the
dedicated remote antenna cable. Tighten the
connector of the remote antenna cable with a
torque of 1 to 1.2 N•m. The minimum bending
radius should be more than 100 mm.
2. Protect the connectors of the FN110 and
remote antenna cable as necessary. For details
of the protection, refer to subsection 4.2.1
“Installation of FN110”.
3. Fix the remote antenna cable to an appropriate
structure to protect the cable from the vibration,
wind, and so on. The minimum bending radius
for fixing in the state maintained for a long
period should be more than 100 mm.
F0503.ai
Figure 5.3
Sealing of the Remote Antenna Cable
CAUTION
• Use the dedicated remote antenna cable
provided by Yokogawa as accessories for
FN110.
• The remote antenna cable and other cables
should not be bundled together.
• Remove the battery pack before installing
FN110. Refer to subsection 8.3 “Replacing
the Battery Pack” for the battery pack
removing.
5.4 Connection of the Input
Signal Cable
Refer to subsection 5.2 “Cable Selection” for the
cable to be used.
How to connect each device refer to the
corresponding item of section 9 “Connection Device
Type”.
5.4.1 Connecting Input Terminal and
Grounding Terminal
F0504.ai
Grounding
terminal
Input terminal
Figure 5.4
Wiring Example
The cable gland is not included. Prepare a cable
gland with a flat gasket matching the electrical
connection.
When M20 female is selected for vertical
connection, tighten the cable gland with a torque of
2 N • m. When G 1/2 female or 1/2 NPT female is
selected for vertical connection, fix the hexagonal
shape part by tool and tighten the cable gland as
shown in Figure 5.5.
F0505.ai
Figure 5.5
Tightening the Cable Gland