<7. Setting Parameters>
7-7
IM 01W03D02-01EN
7.4.3 Checking with Integral Indicator
NOTE
If an error is detected by running self-
diagnostics, an error number is displayed on the
integral indicator. If there is more than one error,
the error number changes at 2 seconds interval.
For details of the alarm codes, refer to section 9
“Connection Device Type”.
F0703.ai
Figure 7.2
Error Check with Integral Indicator
Table 7.3
Diagnostic Status
Bits
Contents
NAMUR NE107
Categorization*
Bit31(MSB)
F:Failure status
---
Bit30
C:Function check status
---
Bit29
O:Out of specification status
---
Bit28
M:Maintenance required status
---
Bit27
Faults in electronics
F
Bit26
Faults in sensor or actuator element
F
Bit25
Installation, calibration problem
C
Bit24
Out of service
C
Bit23
Outside sensor limits
O
Bit22
Environmental conditions out of device specification
O
Bit21
Fault prediction: Maintenance required
M
Bit20
Power is critical low: maintenance need short-term
M
Bit19
Power is low: maintenance need mid-term
M
Bit18
Software update incomplete
C
Bit17
Simulation is active
C
Bit16
Faults due to process influence
F
Bit15
Faults due to non-compliance with specified operating conditions
F
Bit14
Other faults
F
Bit13-Bit09
reserved by WCI
---
Bit08
Connected device: Failure
F
Bit07
Connected device: Function Check
C
Bit06
Connected device: Out of Specification
O
Bit05
Connected device: Maintenance required
M
Bit04-Bit01
vendor specific area
---
Bit00
Detail information available
---
1: available
0: no available
*:NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”