<4. Installation>
4-1
IM 01W03D02-01EN
4. Installation
4.1 Precautions
• Before installing FN310, read the cautionary
notes in subsection 2.4 “Selecting the
Installation Location”.
• For additional information on the ambient
conditions allowed at the installation
location, refer to subsection 10.1 “Standard
Specifications”.
IMPORTANT
Connector Protection
The FN110 terminal is covered with a cap during
shipping. Keep the cap attached until connecting
the FN110 or remote antenna cable to protect
the inside connection part. The unscrewed
cap should be stored in order to replace it
immediately after the FN110 or remote antenna
cable is removed. If there is a possibility that
get wet with water, order FN310 with optional
specification for a protection cap.
Installation Work
• When performing on-site pipe fitting work
that involves welding, use case to prevent
the welding current to damage the FN310.
• Do not use the FN310 as a foothold.
NOTE
• Before using FN310, install FN110. For detail
on how to install FN110, refer to subsection
4.2.1 “Installation of FN110”.
•
To connect FN310 to the field wireless
network, information for connecting to
the field wireless devices needs to be
set beforehand. Refer to subsection 6.3
“Connecting to the Field Wireless Network”.
4.2 Mounting
This product is installed on a 50A (2-inch) pipe.
Mounting on a 50A (2-inch) pipe
FN310 is installed on a 50A (2-inch) pipe with
mounting bracket. It supports both of a horizontal
pipe and a vertical pipe. Refer to subsection 4.2.2
“Mounting on a 50A (2-inch) Pipe” for details. For
detail on how to install FN110, refer to subsection
4.2.1 “Installation of FN110”. For using remote
antenna cable, refer to subsection 5.3 “Installation
and Connection of FN110”.
F0401.ai
FN110
Mounting bracket
Modbus Device
2-inch pipe
FN310
Figure 4.1
Direct Mounting of FN110
F0402.ai
FN110
FN310
Mounting
bracket
2-inch pipe
Remote antenna cable
Modbus Device
Mounting bracket
2-inch pipe
Figure 4.2