<2. Notes on Handling>
2-10
IM 01W03D02-01EN
WARNING / AVERTISSEMENT
• DANGER POTENTIEL DE CHARGES
ÉLECTROSTATIQUES
- QUAND LE MATÉRIEL EST
UTILISÉ DANS DES ENDROITS
DANGEREUX, ÉVITER TOUTE
ACTION QUI GENERENT CHARGES
ELECTROSTATIQUES, COMME
FROTTANT AVEC UN CHIFFON SEC
•
QUAND LE MATÉRIEL EST UTILISÉ DANS
LA ZONE 0, IL DOIT ÊTRE INSTALLÉE TELLE
QUE, MÊME EN CAS D’INCIDENTS RARE,
SOURCES D’ALLUMAGE DUE AUX IMPACTS
ET SPARKS FRICTION EST EXCLUE
• POUR ÉVITER ALLUMAGE DES
ATMOSPHÉRES INFLAMMABLES OU
COMBUSTIBLES, LISEZ, COMPRENDRE
ET RESPECTER ELS PROCÉDURES
D’ENTRETIEN DU CONSTRUCTEUR
• UTILISER UNIQUEMENT DES
ACCUMULATEUR F9090FC OU F9090GC
(YOKOGAWA)
• LA BATTERIE PEUT ÊTRE REMPLACÉ
DANS DES ENDROITS DANGEREUX.
BATTERIE POSSÈDE UNE RÉSISTANCE
DE SURFACE QUI EST SUPÉRIEURE À 1
G OHM ET DOIT ÊTRE INSTALLÉ DANS
L’ENVELOPPE DE L’ÉQUIPEMENT, SOIN
PENDANT LE TRANSPORT ET DEPUIS LE
POINT DE L’INSTALLATION POUR ÉVITER
CHARGE ÉLECTROSTATIQUE BUILD-UP
• CELLULES DOIVENT ÊTRE CHANGÉ
DANS UN ENDROIT UNCLASSIFIED
SEULEMENT
• SUBSTITUTION DE COMPOSANTS PEUT
IMPAIR LA SÉCURITÉ INTRINSÈQUE
• Be sure to use the specified battery pack
and batteries. For details, refer to section 8.5
“Handling Batteries.”
• With an intrinsically safe products, the
battery pack is replaceable in a hazardous
area. During the replacement work, make
sure that dust and water droplets do not
enter inside the products. For details on how
to replace the battery pack, refer to section
8.3 “Replacing the Battery Pack.”
2.6.3 ATEX Certification
(1) Technical Data
Caution for ATEX Intrinsically safe type.
Note 1. Model FN310 Field Wireless Multi-Protocol
Module(RS485 Modbus Protocol) with
optional code /KS27 for potentially
explosive atmospheres:
• Certificate number: FM15ATEX0071X
• Applicable Standards: EN IEC 60079-0,
EN 60079-11, EN 60079-28
• Type of Protection and Marking code:
II 1G Ex ia op is [ia IIC Ga] IIB T4 Ga
• Group: II
• Category: 1 G
• Amb. Temp.: –40 to 70°C (–40 to 158 °F)
• Enclosure:
IP66 in accordance with only IEC 60529
• Signals
Terminals: RS485 Modbus communication
Connector: RS485 Communication
• Dielectric strength
Dielectric strength≥ 500 V AC, r.m.s.,1 min
Note 2. Electrical Parameters
(Refer to the Control Drawing)
Note 3. Installation
• Installation should be in accordance with
local installation requirements.
(Refer to the Control Drawing)
[Control Drawing, IFM045-A86 for ATEX
Certification]
F0208.ai
4
5
3
2
1
1
2
3
4
5
6
Wireless
Communication
Connector
Terminal
Sensor
Input
Not used
Hazardous Area
Group IIC
Hazardous Area
Group IIB
Hazardous Area
Group IIC
Ui
≥
Uo
Ii
≥
Io
Pi
≥
Po
Ci
≤
Co - Ccable
Li
≤
Lo - Lcable
Ui
≥
Uo
Ii
≥
Io
Pi
≥
Po
Ci, Li: See *1
Wireless Communication
(Connector)
Uo :
5.88 V
Io :
483 mA
Po :
779 mW
Co :
5.82 µF
Lo :
25 µH
Sensor Input
(Terminal 1 to 4)
Uo :
5.88 V
Io :
145 mA
Po :
213 mW
Co :
43 µF
Lo :
1.6 mH
FN310
Field Wireless
Multi-Protocol Module
(Modbus)
Intrinsically Safe
Apparatus (1)
Terminal
Intrinsically Safe Apparatus (2)
Not used
*1 As allowable connection values of an Intrinsically Safe
Apparatus (2), the following conditions of (a) or (b) must
be satisfied.
(a) {( Li × 100 ≤ Lo) or (Ci × 100 ≤ Co)} and {Li ≤ (Lo -
Lcable) and Ci ≤ (Co - Ccable)}
(b) { Li ≤ (Lo / 2 - Lcable) and Ci ≤ (Co / 2 - Ccable)}
and [{(Ci + Ccable) ≤ 600 nF for Group IIC} or {(Ci +
Ccable) ≤ 1μF for Group IIA, IIB}]