<9. Connection Device Type>
9-15
IM 01W03D02-01EN
Object ID Attribute
ID
Label
Description
Default value Handling
*
1
4.
TRANSDUCER
block
1
Tag Description Memo field available to write anything.
Transducer
W(P)
2
Model
Indicates the model name of the FN310.
---
R
3
Serial Number
Indicates the serial number of the FN310.
---
R
4
Display
Selection
Select PV Value displaying on the integral indicator.
0: AI1 (default)
1: AI2
2: AI3
3: AI4
AI1
W(P)
5
LCD Intermittent
Time
Select the off time of the integral indicator.
0: Continuous mode
1: Intermittent mode
(off: 5 seconds, display: 2 seconds)
2: Intermittent mode
(off: 10 seconds, display: 2 seconds)
3: Intermittent mode
(off: 30 seconds, display: 2 seconds)
4: Intermittent mode (default)
(off: 60 seconds, display: 2 seconds)
5: Off mode
Intermittent
mode
(off: 60
seconds,
display: 2
seconds)
W(P)
6
LCD Exp Mode Select the notation of the integral indicator.
0: radix notation (default)
1: exponential notation
radix notation
W(P)
7
Wireless Status
Indicates the wireless communication status.
Bits
Contents
Value
Bit7-3
reserved
---
Bit2
Contract status
(Client/Server)
0: Not established
1: Established
Bit1
Contract status
(Publish)
0: Not established
1: Established
Bit0
Join status
0: Idle
1: Joined
---
R
8
Measurement
Rate
Indicates the publish period.
Unit: second
---
R
10
Special Cmd
Special function parameter.
0: Normal mode (default)
1: Deep-sleep mode
Normal mode
W
11
Sensor Type
Select the type of sensor to be connected to the
FN310.
20: SENCOM sensor(default)
21: Not Used
SENCOM
sensor
W(P)
8.
SENCOM
Interface
block
64
Vendor Name
Indicates the Vendor Name of Modbus device
connected to the FN310.
YOKOGAWA
R
65
Product Code
Indicates the Product Code of Modbus device
connected to the FN310.
---
R
66
Major Minor
Revision
Indicates the Device Revision number and
Software Revision number of Modbus device
connected to the FN310.
Format: dd-ssss
dd: Device Revision (Hexadecimal, 2 digit)
ssss: Software Revision (Hexadecimal, 4
digit)
---
R