background image

POWERDIST AUST PTY LTD 

1/14 

 

DONE BY: CDP / JHI 

 

REV 1 

DATE: 01/05/12 

 

P

OWERDIST 

 

AUST PTY LTD

 

 

 

 

 

 

 

 

PO Box 197 

 

 

 

Kotara NSW 2289 

 

 

 

Unit 3, 44 Park Ave  

 

 

 

Adamstown NSW 2289 

 

 

 

Tel: (+61) 02 4965 5771 

 

 

 

Fax: (+61) 02 4965 5772 

 

 

 

email: [email protected]

 

 

 

INSTRUCTIONS TO REPLACE A 

DECS125-15 BY A DECS-200 

 

 

    

Содержание DECS125-15

Страница 1: ...Y CDP JHI REV 1 DATE 01 05 12 POWERDIST AUST PTY LTD PO Box 197 Kotara NSW 2289 Unit 3 44 Park Ave Adamstown NSW 2289 Tel 61 02 4965 5771 Fax 61 02 4965 5772 email info powerdist com au INSTRUCTIONS TO REPLACE A DECS125 15 BY A DECS 200 ...

Страница 2: ...GE SENSING 7 CURRENT SENSING 7 BUS SENSING 7 SETPOINT ADJUSTMENT 8 REGULATION MODE SELECTION 8 3 2 DIFFERENCES DECS 125 15 DECS 200 9 POWER INPUT 9 CROSS CURRENT COMPENSATION CCC 9 ACCESSORY INPUT 10 ALARM CONTACT OUTPUT 10 3 3 DECS200 REQUIREMENTS 11 AUXILIARY POWER SUPPLY 11 EXCITATION ON OFF 11 ALARM RESET 12 3 4 DECS200 NEW FEATURES 12 PREPOSITION OPTIONAL 12 AUTO MANU MODE OPTIONAL 12 COMMUNI...

Страница 3: ...POWERDIST AUST PTY LTD 3 14 DONE BY CDP JHI REV 1 DATE 01 05 12 1 MECHANICAL LAYOUT 1 1 DECS125 15 DECS63 15 DECS32 15 Dimensions are indicated in inches and in millimetres in brackets ...

Страница 4: ...POWERDIST AUST PTY LTD 4 14 DONE BY CDP JHI REV 1 DATE 01 05 12 1 2 DECS200 PROJECTION MOUNTING ...

Страница 5: ...POWERDIST AUST PTY LTD 5 14 DONE BY CDP JHI REV 1 DATE 01 05 12 FRONT DOOR MOUNTING BRACKET ...

Страница 6: ...5 CTCC 5A the CCC with the DECS200 Please refer B6 CTCC COM to chapter 3 2 for more details PARALLELING CONTROL 52L A35 52L M 52M A36 COM VAR PF CONTROL 52J A37 52J K 52K A38 COM EXTERNAL ADJUST 6U A29 RAISE 7 A30 COM 6D A31 LOWER AUX ADJUST Biasing A8 GND Accessory input can be a A A9 V 4 20mA signal if preferred Refer to chapter 3 2 B A10 V for more details ALARM ALRM A15 Relay 1 3 programmable ...

Страница 7: ... replace the power output of the DECS32 15 DECS63 15 DECS125 15 Forcing output 10s 200Vdc 30Adc VOLTAGE SENSING DECS125 15 DECS200 Voltage sensing single or 3 phases range from 100Vac to 500Vac with 50Hz 120 to 600Vac with 60Hz CURRENT SENSING DECS125 15 DECS200 Current sensing secondary CT 1A or 5A BUS SENSING DECS125 15 DECS200 Voltage matching single phase range from 100Vac to 500Vac with 50Hz ...

Отзывы: