Installing and Wiring Option Boards
2-
41
PG-D2
The terminal specifications for the PG-D2 are given in the following table.
* 5 VDC and 12 VDC cannot be used at the same time.
PG-X2
The terminal specifications for the PG-X2 are given in the following table.
* 5 VDC and 12 VDC cannot be used at the same time.
Table 2.17 PG-D2 Terminal Specifications
Terminal
No.
Contents
Specifications
TA1
1
Power supply for pulse generator
12 VDC (±5%), 200 mA max.*
2
0 VDC (GND for power supply)
3
5 VDC (±5%), 200 mA max.*
4
Pulse input + terminal
Line driver input (RS-422 level input)
Maximum response frequency: 300 kHz
5
Pulse input - terminal
6
Common terminal
–
7
Pulse monitor terminal
Line driver output (RS-422 level output)
8
Pulse monitor output - terminal
TA2
(E)
Shield connection terminal
–
Table 2.18 PG-X2 Terminal Specifications
Terminal
No.
Contents
Specifications
TA1
1
Power supply for pulse generator
12 VDC (±5%), 200 mA max.*
2
0 VDC (GND for power supply)
3
5 VDC (±5%), 200 mA max.*
4
A-phase + input terminal
Line driver input (RS-422 level input)
Maximum response frequency: 300 kHz
5
A-phase - input terminal
6
B-phase + input terminal
7
B-phase - input terminal
8
Z-phase + input terminal
9
Z-phase - input terminal
10
Common terminal
0 VDC (GND for power supply)
TA2
1
A-phase + output terminal
Line driver output (RS-422 level output)
2
A-phase - output terminal
3
B-phase + output terminal
4
B-phase - output terminal
5
Z-phase + output terminal
6
Z-phase - output terminal
7
Control circuit common
Control circuit GND
TA3
(E)
Shield connection terminal
–
TOE-S616-60.1.book 41 ページ 2017年8月4日 金曜日 午後3時41分