Protective and Diagnostic Functions
7-
15
Corrective Actions for Control Faults (CF)
Meaning of CR Error Codes
U1-50
Meaning
00
Stop error
01
Magnetic flux calculation error 1
02
Magnetic flux calculation error 2
04
Speed estimator gain adjustment fault
08
Low-speed regeneration fault
10
Zero-speed fault
20
Rotation direction limit fault
U1-50 = 01,02
U1-50 = 00,01,
02,08
U1-50 = 00
U1-50 = 02
U1-50 = 04
U1-50 = 08
U1-50 = 10
U1-50 = 20
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
CF occurs
Are the motor and
Inverter connected
properly?
Fix the wiring.
Are the motor
constants set
correctly?
Execute autotuning for the
motor constants.
Has autotuning been
executed for line-to-line
resistance?
Execute autotuning for the
line-to-line resistance.
Are the torque limit settings (L7-01
to L7-04, analog input) or the torque
reference input too small?
Increase the torque limit
or torque reference until
is it within the allowable
range for the machine.
Is the stopping
method appropriate?
If deceleration stop is not
possible or unnecessary
for the machine, set b1-0
3
to 1 (coast to stop).
Is an operation reference
being input while the motor
is coasting?
· Input the operation reference
after the motor stops.
·
S
et b
3
-01 to 1 or
3
(speed
search enabled).
What is the CF error
code (U1-50)?
Adjust the speed estimator's
integral time (N4-07) or
proportional gain (N4-08).
If the machine rotates only in the
same direction as the sign of the
speed limit, set b1-10 to 1.
· If the machine rotates only in the
same direction as the sign of the
speed limit (winding operation), set
d5-07 to 1.
· Ensure that the motor's speed is
not 0 or that it does not rotate in
the opposite direction.
· If the machine rotates in the
opposite direction to the sign of
the speed limit (unwinding
operation), set d5-07 to 0.
·
S
tart with speed control and then
switch to torque control when the
frequency exceeds
3
Hz.
Use in open loop vector 1 control.
Refer to
Autotuning
on page
4-9. Execute autotuning after
the control method is
changed.
Refer to
Autotuning
on page
4-9. Execute autotuning
after changing cables.
Refer to
Torque Limits: L7
on page 5-66. In particular, if
the regenerative torque limit
has been reduced to prevent
overvoltages, set L3-11 to 1
and set the regenerative
torque limit to a large value.
Refer to
Speed Search
on page 6-65.
Refer to
Procedure for
Increasing the Speed
Response (PRG 102
only)
on page 4-33.
Refer to
Speed/Torque
Control Switching Function
on page 6-136.