Standard Inverter Specifications
9-
3
400 V Class
* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. A 3-wire transformer (optional) is required on the power supply for 12-phase rectification.
* 3. The Inverter does not support UL/CE standards when a DC power supply is used.
Table 9.2 400 V Class Inverters
Model Number CIMR-G7A
40P4
40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
Max. applicable motor output
(kW)
*1
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
Rated input current (A)
2.2
4.1
5.8
7.4
10.8
18
25
32
40
46
Rated output capacity
(kVA)
1.4
2.6
3.7
4.7
6.9
11
16
21
26
32
Rated output current (A)
1.8
3.4
4.8
6.2
9
15
21
27
34
42
Max. output voltage (V)
3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency
(Hz)
Frequencies supported up to 400 Hz using constant setting
Rated voltage (V)
Rated frequency (Hz)
3-phase AC power supply of 380, 400, 415, 440, 460, or 480 V at 50/60 Hz, or DC power supply of 510 to 680 V
*3
Allowable voltage
fluctuation
+10%, -15%
Allowable frequency
fluctuation
±5%
Measures for
power supply
harmonics
DC reactor
Optional
Built in
12-phase
rectification
Not possible
Possible
*2
Model Number CIMR-G7A
4022
4030
4037
4045
4055
4075
4090
4110
4132
4160
4185
4220
4300
Max. applicable motor output
(kW)
*1
22
30
37
45
55
75
90
110
132
160
185
220
300
Rated input current (A)
57
72
88
107
141
182
215
264
297
332
407
495
666
Rated output capacity
(kVA)
40
50
61
74
98
130
150
180
210
230
280
340
460
Rated output current (A)
52
65
80
97
128
165
195
240
270
302
370
450
605
Max. output voltage (V)
3-phase, 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Max. output frequency
(Hz)
Frequencies supported up to 400 Hz using constant setting
Max. voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460, or 480 VAC, 50/60 Hz
Allowable voltage
fluctuation
+10%, -15%
Allowable frequency
fluctuation
±5%
Measures for
power supply
harmonics
DC reactor
Built in
12-phase
rectification
Possible
*2
Out
put
r
at
ings
Po
wer s
uppl
y characteris
tics
Ou
tput
rat
ing
s
Pow
er s
upply char
act
eri
sti
cs