User Constant Tables
5-
35
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. When E1-13 (Base Voltage) is set to 0.0, control is performed with E1-13 equal to E1-05 (Max. Voltage).
* 5. The setting range for open-loop vector 2 control is 0 to 66.0 (0 to 132.0 for
PRG 103
).
For the 400 V Class, there are limitations on the maximum output frequency depending on the setting of the carrier frequency and capacity.
The maximum output frequency for 400 V, 90 to 110 kW is 250 Hz. The maximum output frequency for 400 V, 132 to 300 kW is 166 Hz.
Motor Setup: E2
User constants for motor 1 are shown in the following table.
E1-11
Mid. output
frequency 2
Set only to fine-adjust V/f for the
output range. Normally, this setting
is not required.
0.0 to
400.0
*5
0.0 Hz
*3
No
A
A
A
A
A
30AH 6-123
Mid
Frequency
B
E1-12
Mid. output
frequency
voltage 2
0.0 to
255.0
*1
0.0 V
*3
No
A
A
A
A
A
30BH 6-123
Mid
Voltage B
E1-13
*4
Base
voltage
0.0 to
255.0
*1
0.0 V
*4
No
A
A
Q
Q
Q
30CH 6-123
Base
Voltage
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
E2-01
Motor rated
current
Sets the motor rated current in
1 A units.
These set values will become
the reference values for motor
protection, torque limits and
torque control.
This constant is automatically
set during autotuning.
0.32 to
6.40
*2
1.90 A
*1
No
Q
Q
Q
Q
Q
30EH
4-8
6-58
6-119
Motor Rated
FLA
E2-02
Motor rated
slip
Sets the motor rated slip in
Hz units.
These set values will become
the reference values for slip
compensation.
This constant is automatically
set during autotuning.
0.00 to
20.00
2.90 Hz
*1
No
A
A
A
A
A
30FH
6-117
6-119
Motor Rated
Slip
E2-03
Motor no-
load current
Sets the motor no-load cur-
rent in 1 A units.
This constant is automatically
set during autotuning.
0.00 to
1.89
*3
1.20 A
*1
No
A
A
A
A
A
310H
6-119
No-Load
Current
E2-04
Number of
motor poles
Sets the number of motor
poles.
This constant is automatically
set during autotuning.
2 to 48 4 poles
No
No
Q
No
Q
Q
311H
6-119
Number of
Poles
E2-05
Motor line-
to-line resis-
tance
Sets the motor phase-to-phase
resistance in
Ω
units.
This constant is automatically
set during autotuning.
0.000
to
65.000
9.842
Ω
*1
No
A
A
A
A
A
312H
6-119
Term Resis-
tance
Con-
stant
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
TOE-S616-60.1.book 35 ページ 2017年8月4日 金曜日 午後3時41分