Trial Operation Procedures
4-
5
V/f Control (A1-02 = 0)
•
Set either one of the fixed patterns (0 to E) in E1-03 (V/f Pattern Selection) or set F in E1-03 to specify a
user-set pattern as required for the motor and load characteristics in E1-04 to E1-13 in advanced program-
ming mode.
•
Perform stationary autotuning for the line-to-line resistance only if the motor cable is 50 m or longer for
the actual installation or the load is heavy enough to produce stalling. Refer to the following section on
Autotuning
for details on stationary autotuning.
V/f Control with PG (A1-02=1)
•
Set either one of the fixed patterns (0 to E) in E1-03 (V/f Pattern Selection) or set F in E1-03 to specify a
user-set pattern as required for the motor and load characteristics in E1-04 to E1-13 in advanced program-
ming mode.
•
Set the number of motor poles in E2-04 (Number of Motor Poles)
•
Set the number of rotations per pulse in F1-01 (PG Constant). If there is a reduction gear between the
motor and PG, set the reduction ratio in F1-12 and F1-13 in advanced programming mode.
•
Perform stationary autotuning for the line-to-line resistance only if the motor cable is 50 m or longer, the
load is heavy enough to stall the motor, or there is a high possibility of overload. Refer to the following
section on
Autotuning
for details on stationary autotuning for the line-to-line resistance.
Open-loop Vector 1 Control (A1-02 = 2)
Perform autotuning. If the motor can be operated, perform rotational autotuning. If the motor cannot be oper-
ated, perform stationary autotuning 1 or 2. Refer to the following section on
Autotuning
for details on autotun-
ing.
Flux Vector Control (A1-02 = 3)
Perform autotuning. If the motor can be operated, perform rotational autotuning. If the motor cannot be oper-
ated, perform stationary autotuning 1 or 2. Refer to the following section on
Autotuning
for details on autotun-
ing.
Open-loop Vector 2 Control (A1-02 = 4)
Perform autotuning. If the motor can be operated, perform rotational autotuning. If the motor cannot be oper-
ated, perform stationary autotuning 1 or 2. Refer to the following section on
Autotuning
for details on autotun-
ing.
Simple operation of a general-purpose
motor at 50 Hz:
E1-03 = 0
Simple operation of a general-purpose
motor at 60 Hz:
E1-03 = F (default) or 1
If E1-03 = F, the default setting in the user setting from
E1-04 to E1-13 are for 60 Hz
Simple operation of a general-purpose
motor at 50 Hz:
E1-03 = 0
Simple operation of a general-purpose
motor at 60 Hz:
E1-03 = F (default) or 1
If E1-03 = F, the default setting in the user setting from
E1-04 to E1-13 are for 60 Hz