Individual Functions
6-
103
Note Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).
Broadcast Data
The following table shows the broadcast data. You can also write this data.
Note Bit signals not defined in the broadcast operation signals use local node data signals continuously.
ENTER Command
When writing constants to the Inverter from the PLC using MEMOBUS communications, the constants are
temporarily stored in the constant data area in the Inverter. To enable these constants in the constant data area,
use the ENTER command.
There are two types of ENTER commands: ENTER commands that enable constant data in RAM, and
ENTER commands that write data to EEPROM (non-volatile memory) in the Inverter at the same time as
enabling data in RAM.
The following table shows the ENTER command data. ENTER command data can only be written.
The ENTER command is enabled by writing 0 to register number 0900H or 0901H.
003DH
Communications error details
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to F
Not used
003EH
kVA setting
003FH
Control method
Register
Address
Contents
0001H
Operation signal
Bit 0
Run Command 1: Operating 0: Stopped
Bit 1
Reverse operation command 1: Reverse 0: Forward
Bits 2 and 3
Not used
Bit 4
External fault 1: Error (set using H1-01)
Bit 5
Fault reset 1: Reset command (set using H1-02)
Bits 6 to B
Not used
Bit C
Multi-function contact input terminal S5 input
Bit D
Multi-function contact input terminal S6 input
Bit E
Multi-function contact input terminal S7 input
Bit F
Multi-function contact input terminal S8 input
0002H
Frequency
reference
30000/100%
Register No.
Contents
0900H
Write constant data to EEPROM
0910H
Constant data is not written to EEPROM, but refreshed in RAM only.
Register No.
Contents