
5
-90
Factory Settings that Change with the Control Method (A1-02)
The factory settings of the following user constants will change if the control method (A1-02) is changed.
Con-
stant
Number
Name
Setting Range
Unit
Factory Setting
Display
V/f
Control
V/f with
PG
Open-
loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
b3-01
Speed search selection
0 to 3
1
2
3
2
–
2
SpdSrch at Start
b3-02
Speed search operating current
0 to 200
1%
120
–
100
–
10
SpdSrch Current
b8-02
Energy-saving gain
0.0 to 10.0
0.1
–
–
0.7
1.0
0.7
Energy Save Gain
b8-03
Energy-saving filter time constant
0.0 to 10.00
0.01 s
–
–
0.50
0.01
0.50
Energy Save F.T
C3-01
Slip compensation gain
0.0 to 2.5
0.1
0.0
–
1.0
1.0
1.0
Slip Comp Gain
C3-02
Slip compensation primary delay time
0 to 10000
1 ms
2000
–
200
–
–
Slip Comp Time
C4-02
Torque compensation primary delay time
constant
0 to 10000
1 ms
200
*5
200
*5
20
–
–
Torq Comp Time
C5-01
ASR proportional (P) gain 1
0.00 to 300.00
0.01
–
0.20
–
20.00
10.00
ASR P Gain 1
C5-02
ASR integral (I) time
0.000 to 10.000
0.001 s
–
0.200
–
0.500
0.500
ASR I Time 1
C5-03
ASR proportional (P) gain 2
0.00 to 300.00
0.01
–
0.02
–
20.00
10.00
ASR P Gain 2
C5-04
ASR integral (I) time 2
0.000 to 10.000
0.001
sec.
–
0.050
–
0.500
0.500
ASR I Time 2
C5-06
ASR primary delay time
0.000 to 0.500
0.001
–
–
–
0.004
0.010
ASR Delay Time
0.035
C6-02
Carrier frequency selection
1 to F
*6
–
6
*7
6
*7
6
*7
1
*8
6
*7
Carrier Freq Sel
C6-03
Carrier frequency upper limit
0.4 to 15.0
*6
0.1 kHz
15.0
*7
15.0
*7
15.0
*7
2.0
–
Carrier Freq Max
d5-02
Torque reference delay time
0 to 1000
1 ms
–
–
–
0
10
Torq Ref Filter
E1-04
E3-02
Max. output frequency (FMAX)
0.0 to 400.0
*4
0.1 Hz
60.0
*3
60.0
*3
60.0
60.0
60.0
Max Frequency
E1-05
E3-03
Max. voltage (VMAX)
0.0 to 255.0
0.1 V
200.0
*3
200.0
*3
200.0
200.0
200.0
Max Voltage
E1-06
E3-04
Base frequency (FA)
0.0 to 400.0
0.1 Hz
60.0
*3
60.0
*3
60.0
60.0
60.0
Base Frequency
TOE-S616-60.1.book 90 ページ 2017年8月4日 金曜日 午後3時41分