5
-38
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The open-loop vector 1 factory settings are given.
* 3. The setting range for open-loop vector 2 control is 0 to 66.0 (0 to 132.0 for
PRG 103
).
E3-02
Motor 2
max.
output
frequency
(FMAX)
To set V/f characteristics in a
straight line, set the same values for
E3-05 and E3-07.
In this case, the setting for E3-06
will be disregarded.
Always ensure that the four frequen-
cies are set in the following manner:
E3-02 (FMAX)
≥
E3-04 (FA) > E3-
05 (FB) > E3-07 (FMIN)
40.0 to
400.0
*3
60.0
Hz
No
A
A
A
A
A
31AH
–
Max
Frequency
E3-03
Motor 2
max.
voltage
(VMAX)
0.0 to
255.0
*1
200.0
V
*2
No
A
A
A
A
A
31BH
–
Max
Voltage
E3-04
Motor 2
max.
voltage
frequency
(FA)
0.0 to
400.0
60.0
Hz
No
A
A
A
A
A
31CH
–
Base
Frequency
E3-05
Motor 2
mid.
output
frequency 1
(FB)
0.0 to
400.0
3.0 Hz
*2
No
A
A
A
No
No
31DH
–
Mid
Frequency
E3-06
Motor 2
mid.
output
frequency
voltage 1
(VC)
0.0 to
255.0
*1
11.0 V
*1*2
No
A
A
A
No
No
31EH
–
Mid
Voltage
E3-07
Motor 2
min.
output
frequency
(FMIN)
0.0 to
400.0
0.5 Hz
*2
No
A
A
A
A
A
31FH
–
Min
Frequency
E3-08
Motor 2
min.
output
frequency
voltage
(VMIN)
0.0 to
255.0
*1
2.0 V
*1*2
No
A
A
A
No
No
320H
–
Min
Voltage
Con-
stant
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Output voltage (V)
Frequency (Hz)
VMAX
E3-03
VC
E3-06
VMIN
E3-08
FMIN
E3-07
FB
E3-05
FA
E3-04
FMAX
E3-02