5
-18
Dwell Functions: b6
User constants for dwell functions are shown in the following table.
b5-15
PID sleep
function
operation
level
Set the PID sleep function
start level as a frequency.
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
1B3H
6-110
PID Sleep
Level
b5-16
PID sleep
operation
delay time
Set the delay time until the
PID sleep function starts in
seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
A
1B4H
6-110
PID Sleep
Time
b5-17
Accel/decel
time for PID
reference
Set the accel/decel time for
PID reference in seconds.
0.0 to
25.5
0.0 s
No
A
A
A
A
A
1B5H
6-110
PID SFS
Time
Con-
stant
Num-
ber
Name
Description
Setting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
b6-01
Dwell fre-
quency at
start
The dwell function is used to output
frequency temporarily when driving
a motor with a heavy load.
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
1B6H
4-33
6-22
Dwell Ref
@Start
b6-02
Dwell time
at start
0.0 to
10.0
0.0 s
No
A
A
A
A
A
1B7H
4-33
6-22
Dwell
Time
@Start
b6-03
Dwell fre-
quency at
stop
0.0 to
400.0
0.0 Hz
No
A
A
A
A
A
1B8H
4-33
6-22
Dwell Ref
@Stop
b6-04
Dwell time
at stop
0.0 to
10.0
0.0 s
No
A
A
A
A
A
1B9H
4-33
6-22
Dwell
Time
@Stop
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Run command ON
Output frequency
Time
b6-03
OFF
b6-01
b6-04
b6-02
TOE-S616-60.1.book 18 ページ 2017年8月4日 金曜日 午後3時41分