Wiring Examples
10-
27
10
Using a Braking Unit and Three Braking Resistor Units in Parallel
This example shows wiring for using three Braking Resistor Units in parallel.
Fig 10.16
THRX
THRX
1
2
TRX
TRX
MB
MC
2MCCB
MA MC
OFF
ON
MC
MC
SA
SA
SA
Braking Resistor Unit
thermal relay trip contacts
Fault contacts
Thermal
protector
Thermal
protector
Thermal
protector
Braking
Resistor
Unit
Braking
Resistor
Unit
Braking
Resistor
Unit
Braking Unit
Thermal switch
Inverter
Motor
Cooling fan
Ground Fault Interrupter or Molded-case Circuit Breaker
3-phase power
supply, 380 to
480 V at 50/60 Hz
Voltage
setting
Ground to 10
Ω
max.
Fault contact outputs
Forward Run Com-
mand (forward run
when ON)
Reverse Run Com-
mand (reverse run
when ON)
Forward Run/Stop
Reverse Run/Stop
Braking Unit
External fault
* Disable the stall prevention during deceleration (set constant L3-04 to 0) when using a Brak-
ing Resistor Unit. If this user constant is not changed to disable stall prevention, the system
may not stop in the set deceleration time.
Level det
ec
tor
A sequence is required to turn OFF the
power supply for the thermal protector trip
contacts of the Braking Resistor Unit.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3