v
480Vac
Table i.3 480Vac Drive Specifications
Model Number CIMR-F7U
40P4
40P7
41P5
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
4022
Rated output capacity
(kVA)
1.4
1.6
2.8
4.0
5.8
6.6
9.5
13.0
18.0
24.0
30.0
34.0
Horsepower
*2
0.5/0.75
1
1.5/2
3
5
-
7.5
10
15
20
25
30
Rated output current
(A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17.0
24.0
31.0
39.0
45.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
150
Current limit
*2
(% of
rated output current)
150
Carrier frequency
*4
2kHz
Maximum output
frequency
300.0Hz
Rated output capacity (kVA)
1.4
1.6
2.8
4.0
5.8
6.6
9.5
13.0
21.0
26.0
30.0
38.0
Horsepower
*2
0.5/0.75
1
1.5/2
3
5
-
7.5
10
15/20
25
30
30
Rated output current (A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17.0
27.0
34.0
40.0
50.4
Overload capacity
*3
(% of rated output
current for 60 sec.)
120
120
120
120
120
120
120
120
107
109
117
107
Current limit (% of
rated output current)
120
Carrier frequency (kHz)
*5
15
15
15
15
15
15
15
15
8
10
10
10
Maximum output
frequency
400.0Hz
Maximum output voltage
3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage)
Model Number CIMR-F7U 4030
4037
4045
4055
4075
4090
4110
4132
4160
4185
4220
4300
Rated output capacity
(kVA)
46.0
57.0
69.0
85.0
110.0
140.0
160.0
200.0
230.0
280.0
N/A
Horsepower
*2
40
50
60
75
100
125/150
-
200
250
300
Rated output current
(A)
60.0
75.0
91.0
112.0
150.0
180.0
216.0
260.0
304.0
370.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
150
Current Limit (% of
rated output current)
150
Carrier frequency
*4
2kHz
Maximum output
frequency
300.0Hz
Rated output capacity
(kVA)
51.0
59.0
73.0
95.0
120.0
140.0
180.0
200.0
230.0
315.0
390.0
510.0
Horsepower
*2
40/50
60
75
100
125
150
200
-
250
300/350 400/450
500+
Rated output current
(A)
67.2
77.0
96.0
125.0
156.0
180.0
240.0
260.0
304.0
414.0
515.0
675.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
107
117
114
108
115
120
108
120
120
107
118
120
Current Limit (% of
rated output current)
120
Carrier frequency (kHz)
*5
8
8
8
5
5
8
5
5
5
2
2
2
Maximum output
frequency
400.0Hz
Maximum output voltage
3-phase, 380, 400, 415, 440, 460 or 480Vac (Proportional to input voltage)
*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit, and
maximum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).
*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor
and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.
*3 Models 2110, 4220, 4300 have an overload rating of 120% of rated output current for 60 seconds.
*4 2kHz is the Maximum carrier frequency value and default carrier frequency value for all models.
*5 Each value shown is the Maximum carrier frequency and default carrier frequency.
O
utp
ut rat
ings
Heavy Du
ty
*1
Norma
l Duty
*1
O
utpu
t rat
ing
s
Heavy Dut
y
*1
No
rm
al Du
ty
*1
Содержание Varispeed f7
Страница 1: ...F7 Drive Programming Manual Model CIMR F7U Document Number TM F7 02...
Страница 2: ......
Страница 8: ...vi Notes...
Страница 158: ...Programming 150 Notes...