Programming 59
The Drive has the capability to control 2 motors independently. A second motor may be selected using a multi-function
contact input (H1-0x = 16). This parameter select the control method for motor 2. The control method for motor 1 is selected
via parameter A1-02.
Fig. 39 Two Motor Switching Set-up
The following is a list of parameters that become effective when motor 2 is selected.
E3-08E
E3-02 Motor 2 Maximum Output Frequency
Setting Range:
0.0 to 400.0 Hz
Factory Default: 60.0 Hz
E3-03 Motor 2 Maximum Output Voltage
Setting Range:
0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
480.0V (480V Models)
E3-04 Motor 2 Base Frequency
Setting Range:
0.0 to 400.0 Hz
Factory Default: 60.0 Hz
Table 12 Motor 2 Parameters
V/f Pattern 2
Motor Setup 2
E3-01
Control Method 2
E4-01
Motor Rated FLA
E3-02
Max Frequency
E4-02
Motor Rated Slip
E3-03
Max Voltage
E4-03
No-Load Current
E3-04
Base Frequency
E4-04
Number of Motor Poles
E3-05
Mid Frequency
E4-05
Terminal Resistance
E3-06
Mid Voltage
E4-06
Leakage Inductance
E3-07
Min Frequency
E4-07
Motor Rated Power
E3-08
Min Voltage
-
-
G5
M
M
Motor 1
Motor 2
F7
Содержание Varispeed f7
Страница 1: ...F7 Drive Programming Manual Model CIMR F7U Document Number TM F7 02...
Страница 2: ......
Страница 8: ...vi Notes...
Страница 158: ...Programming 150 Notes...